HAMWORTHY HEATING LTD
MILBORNE 500 SERIES
500001130/A
45
No Desc. Lower
Limit
Family Upper
Limit
Default
Value
Note Specification Pc
Screen
35 T4
Frost
protection
-30°C G
15°C
3 Anti
frost
Also on
T1=5°C
fixed
setting
Temperature for starting frost
protection T4. If T4<= this value or
T1 <= 5°C then the pump start
(*)
.
If after 10 minutes T1 is not over 5°
C -> one burner starts at the
maximum power until T1>= 20°C. If
after 10 minutes T4 is still under this
value then pump
(*)
run until T4 >
this value.
CH_
high
36 Gas
type
1 G
7
1
1 = NG with flue gas duct < 15m lg
2 = NG with flue gas duct > 15m lg
3 = LPG with flue gas duct <15m lg
4 = LPG with flue gas duct >15m lg
5 = town gas
6 = Gas F
7 = Gas G
Gas
Type
37 T_out
_min
-20°C G
30°C
0 Climatic
curve
regulation
Outside temperature at which
maximum flow temperature is
required. High-limited by
T_out_max
CH_
high
38 T_out
_max
0°C G 30°C 18
Climatic
curve
regulation
Outside temperature at which
minimum flow temperature is
required. Low-limited by
T_out_min.
Above this value the heating
system will be turned off
(Summer shutdown)
CH_
high
39 T_out
_correct
-30°C
G
30°C
0
Calibration / correction of outside
temperature
CH_
high
40 P.reduce
emergency
10°C SL
80°C 70°C
Sets
the
maximum
flow
temperature permitted when the
emergency mode is used
Slave
41 Parameter
reset
0
G
1
0
1 = Reset slaves to factory
default
Setting the value of ‘1’ all the
default values are restored
EXCEPT GAS TYPE NUMBER,
PARAMETER 36
G
42
43
(*) This pump is
a)
The general pump; if the 3rd pump is set as
general
b)
The high pump; if the 3rd pump is set as
low pump.
0