HAMWORTHY HEATING LTD
MILBORNE 500 SERIES
500001130/A
14
Components for Individual Flues per 50kW Boiler Module
50 mm diameter flue components for use with Milborne 501 and 502 boilers.
For use on applcations consisting of B23 type flue configurations, where combustion air is taken from within the
boiler house, and C53 room sealed twin duct systems where combustion air is taken directly from outside and
ducted to the boiler.
Maximum equivalent length for this flue system is 30 metres from boiler to terminal for B23 applications, and from
air inlet terminal to flue terminal for C63 applications.
Equivalent lengths for 90° bends is 4 metres with 3 metres equivalent length for a 45° bend.
Pictorial View
Description
HHL Part No.
Polypropylene
45°
bend
ø50
mm
Polypropylene 90° bend ø50 mm
573407109
573407047
Polypropylene pipe ø50 mm x 250mm
Polypropylene pipe ø50 mm x 500mm
Polypropylene pipe ø50 mm x 1000mm
Polypropylene pipe ø50 mm x 1500mm
573407111
573407112
573407113
573407114
Cravat for flat room ø50 mm
573407115
Cravat for pitched roof ø50 mm
573407116
Stainless steel horizontal wall terminals ø50 mm
573407117
Twin duct horizontal flue discharge / air intake kit.
Consisting of:
2 x 90° bends
2 x ø50 mm x 500mm pipe
2 x ø50 mm x 250mm pipe
2 x Stainless steel wall terminals
573407119
Twin duct vertical flue discharge with horizontal air
intake kit for flat roofs. Consisting of:
1 x 90° bend
2 x ø50 mm x 500mm pipe
1 x ø50 mm x 250mm pipe
1 x Stainless steel wall terminals
1 x cravat for flat roof
573407121
Twin duct vertical flue discharge with horizontal air
intake kit for pitched roof. Consisting of:
1 x 90° bend
2 x ø50 mm x 500mm pipe
1 x ø50 mm x 250mm pipe
1 x Stainless steel wall terminals
1 x cravat for pitched roof
573407123
Polypropylene condensate discharge kit. To
remove condensate from vertical and horizontal
flue sections.
573407110
Polypropylene 50mm vertical flue terminal.
573407131