HAMWORTHY HEATING LTD
MILBORNE 500 SERIES
500001130/A
27
14.0 Programmable Room Thermostat
The high temperature and low temperature heating
circuits may have an enhanced level of control by
using the 7 day programmable room thermostat.
Offering independent switching times for each week
day the thermostat offers the flexibility required in
buildings with sporadic heating requirements as well
as the more traditional occupancy trends.
Technical data
Power supply = 2 x 1.5V battery
Normal temperature range T1 = 5 - 30°C
Night set-back range T2 =
=
6°/14°/16°/18°C
Temperature updating = Once/minute
Room temperature switching hysteresis
= 0.2° - 0.8°C
Contacts rating = Max 250V / 5A
Internal frost protection = 6°C
Minimum setting period = 1 Hour
Locating the thermostat
The thermostat should be positioned in the area of
the building most critical for comfort. Within this area
the thermostat must be positioned away from heat
sources such as radiators, sun rays and kitchens.
Additionally the thermostat must be located away
from sources of draught such as doors, windows
and ventilation grilles. All of these can lead to false
readings at the thermostat.
INCORRECT LOCATIONS
CORRECT LOCATIONS
9
8
Mounting the thermostat
The thermostat is suitable for wall with rear cable entry. Alternatively the thermostat may also be mounted to a
standard electrical back box or round conduit box.
Fig 13.4 - Thermostat Mounting