APS-7000 Series User Manual
120
10.
Go to the
Fset
setting set the frequency of the
step. Not applicable for Trans1 and Trans2.
Fset
45.00 ~ 500.0Hz (1000Hz optional)
11.
Go to the
Trig Out
setting and set the state of
the trigger out pin at the start of each step.
Trig Out HI, LO
12.
Lastly, go to the
Repeat
parameter select the
number of times the simulation will repeat the
Normal1-Trans1-Abnormal-Trans2-Normal2
sequence of steps. A value of 0 will set the
number of repetitions to infinite.
Repeat
1 ~ 9999, 0(infinite)