APS-7000 Series User Manual
118
Simulate Settings
Entering the
Simulate Menu
1.
Press
Test
.
Test
2.
Press
Mode[F1]
and use the scroll wheel to
select
SIMULATE
and then press
Enter
.
Simulate Mode
F1 Mode
Steps
3.
Use the scroll wheel to go to the
Step
setting
and press
Enter
.
4.
Use the scroll wheel to select one of the
simulation steps and press
Enter
.
Steps
Initial, Normal1, Trans1, Abnormal,
Trans2, Normal2
5.
Go to the
Time
setting and set the duration of
the step.
Time
0.01 ~ 999.99s, 0(Trans 1 and
Trans2)
Note: For Trans1 and Trans2, it
supports a value of 0, which will
skip the step.