I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual
The Intelligent Solution
20
Fire signal
cannot be
cleared
a) There are obscuration on the optical
pathway between the detector and
the reflector.
b) The angle of optical pathway has
changed and need to be aligned
again.
c) The emitting diode or circuit
damaged.
d) The photodiode or amplifying circuit
damaged.
If the problems are
mentioned in a), b),
commission once again.
If in c), d), replace the
component with problem.
The control
panel can’t
receive
fire or fault
signals.
No registration.
Register again.
X Maintenance
1. If the detector gives fault signal after working for a long time, first
check whether the detector is damaged or not, and make sure that it
is fixed to the wall or other fittings. Then check whether it is the
accumulating dust and positional excursion, causing compensation
fault, then consider other types of fault.
2. If emitting window, receiving window and reflector surface are found
contaminated, clean them with soft cloth and alcohol (avoid
scraping). Never use water or other chemicals. Commission the
detector again after cleaning and make it in monitoring state.
3. The detector is fire protection product, whose operation must be
well recorded by the personnel on duty and shift.
4. Personnel on duty should be familiar with the functions and
operation process of the device to avoid mis-operation.
5. Test alarm function once half a year.
Содержание I-9105R