b) When space height is between 5m and 8m, the detector and
reflector should be mounted on the two facing walls 0.5m to 1m
from the ceiling, as shown in Fig. 5.
Detector
Reflector
7m
6m
Fig. 5
c) When space height is more than 8m, the roof is normally
gabled without ceiling, the detector and reflector should be
mounted on the two facing walls about 8m from the floor, ensuring
that the vertical distance between the detector/reflector and top of
the building is not less than 0.5m, as shown in Fig. 6. The distance
should be 7m from the detector to the floor.