turned off.
4.
Failed Detector
During testing, repair failing detectors according to directions in
Section
IX Troubleshooting
and
X Maintenance
, and test again, if
they fail again, return them to factory for repair.
VII Cautions
1. Power up only after all devices are well connected.
2. Adjust the detector after installation and maintenance.
3. Under adjusting condition, both the detector loop and fault output
contact transmit fault signal.
4. The detector base should be fixed directly on solid wall or frame
that will not be deformed by vibration. Any deformable material
such as paperboard, plastic board, foam board or thin wood board
should not be placed between the base and the wall or the bracket.
VIII Operation
The detector can be simply programmed by a hand held programmer.
Address, device type and sensitivity level of the detector can be set with
a programmer. Open the detector’s top cover, connect I
2
C cable of hand
held programmer (PS/2 cable) with XT3 of the detector. Turn on the
power of hand held programmer, input 2, 5, 9 and
Function
to enter I
2
C
programming mode, the screen shows a “0”. After carrying out operation
needed, input 2, 5, 9 and
Function
again to exit I
2
C programming mode
and return to power-on state
1. Reading
Information
The hand held programmer can conveniently get original information like
address code, sensitivity level and device type. Refer to details below:
z
Enter
I
2
C programming mode, the screen shows a “0”.
z
Press
Test
, the screen shows the address code of the
detector.