I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual
The Intelligent Solution
15
step d).
If green LED illuminates continuously, it means the received light is
quite strong, you can go straight to step d).
Note:
Observe the detector’s optical pathway carefully to ensure
that the received light signal is reflected by the reflector rather
than by obscurations like wall, ceiling, or pillar. If uncertain,
verify by covering the reflector with opaque objects.
d
)
Put on the top cover gently, and screw the two bolts on the cover.
e
)
The green LED illuminates continuously. Put the magnet of
commission tool close to the zone where marked
○
M
until yellow LED
illuminates constantly, then remove the
commission tool
quickly and
make sure there is no obscuration on the optical pathway. About 5
seconds later, the detector begins to adjust automatically. Yellow LED
flashing means weak light, green LED flashing means strong light. If
red LED, yellow LED and green LED flash alternately, this means the
detector failed to adjust automatically and cannot enter normal
monitoring state. Please open the detector’s top cover and do
adjustment from step b). If yellow LED and green LED illuminate no
more, and red LED flashes periodically, this means the detector is at
the best position and has entered normal monitoring state. The
commission is finished.
2.
Fire alarm test
After the detector has been in normal monitoring state for 20
seconds, cover the receiving window and emitting window with the
IR Light Filter (please use the part for fire alarm test), the detector
should report fire alarm in 30 seconds and red LED should turn on.
3.
Fault test
Cover the receiving or emitting window of the detector quickly with
the IR Light Filter (please use the part for commission) to obscure
the optical pathway. Yellow LED of the detector should be turned on.
Taking off the filter immediately, yellow LED of the detector should be