I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual
The Intelligent Solution
cannot be mounted northward, then place the detector on the west
wall. For applications where sunlight can reach the detector after
reflected, please consider mounting a sunshade over the
detector’s optical pathway or contact our field application engineer
for a solution.
3. Mounting
1) Setting Length of Optical Pathway
Before installation, you need to set the length of optical pathway
first by setting device type of the detector. The detector can work at
two levels of length. When mounting distance between the
detector and the reflector is not less than 40m (but not more
than100m), the detector type should be set at “52” (factory default).
When the mounting distance between the detector and the
reflector is less than 40m (but more than 8m), the detector type
should be set at “51”. Refer to Section
VIII Operation
for detailed
setting methods.
2) Mounting the detector
Align the detector and the reflector horizontally on the two facing
walls in monitoring area, as shown in Fig. 8
Fig. 8