B401B Plug-in Detector Base

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue

St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing 

Please thoroughly read the System Sensor manual I56-407,

Guide for Proper Use of System Smoke Detectors

, which pro-

vides detailed information on detector spacing, placement,
zoning, wiring, and special applications. Copies of this man-
ual are available at no charge from System Sensor. (For instal-
lations in Canada, refer to CAN4-S524, 

Standard for the

Installation of Fire Alarm Systems

, and CEC Part 1, Sec. 32.)

NOTICE:

This manual should be left with the owner/user

of this equipment.

IMPORTANT:

The detector used with this base must be

tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned
at least once a year.

Specifications

Base Diameter:

6.2 inches (15.7 cm)

Base Height:

1.1 inches (2.8 cm)

Weight:

0.3 lb. (130 g)

Mounting:

4-inch square box with or without plaster ring. Min. Depth–1.5 inches
4-inch octagon box. Min. Depth–1.5 inches
3

1

2

inch octagon box. Min. Depth–1.5 inches

Operating Temperature Range:

0° to +49°C (32° to 120°F)

Operating Humidity Range:

10% to 93% Relative Humidity, noncondensing

Electrical Ratings

— 

includes base and detector

System Voltage:

12/24 VDC

Maximum Ripple Voltage:

4 Volts peak to peak

Start-up Capacitance:

0.02 

µ

F Maximum

Standby Ratings:

8.5 VDC Minimum; 35 VDC Maximum
120 

µ

A Maximum

Alarm Ratings:

4.2 VDC Minimum at 10 mA; 6.6 VDC Maximum at 100 mA
(Alarm current must be limited to 100 mA by the control panel. If used, the RA400

remote lamp operates within specified detector alarm currents.)

Reset Voltage:

2.5 VDC Minimum

Reset Time:

0.3 Seconds Maximum

Start-up Time:

34.0 Seconds Maximum

For use with the following smoke detectors: 
1451, 2451, and 2451TH

General Description

The B401B plug-in detector base is used with System
Sensor model 2451 and 2451TH photoelectronic detector
heads and model 1451A ionization detector heads. The
capability of plugging these detectors into a variety of spe-
cial bases makes them more versatile than equivalent
direct-wired models. Refer to the System Sensor catalog for
other available plug-in detector bases.

This base is intended for use in 2-wire systems, with screw
terminals provided for power, ground, and remote annun-
ciator connections. 

Содержание B401B

Страница 1: ...s 31 2 inch octagon box Min Depth 1 5 inches Operating Temperature Range 0 to 49 C 32 to 120 F Operating Humidity Range 10 to 93 Relative Humidity noncondensing Electrical Ratings includes base and detector System Voltage 12 24 VDC Maximum Ripple Voltage 4 Volts peak to peak Start up Capacitance 0 02 µF Maximum Standby Ratings 8 5 VDC Minimum 35 VDC Maximum 120 µA Maximum Alarm Ratings 4 2 VDC Min...

Страница 2: ...responding properly in the event of a fire For signal wiring the wiring between interconnected detectors it is recommended that the wire be no smaller than 18 gauge 1 0 square mm Wire sizes up to 12 gauge wire 2 5 square mm may be used with the base For best system performance the power and loop wires should be twisted pair and installed in separate grounded conduit to protect the loop from extran...

Страница 3: ...wiring has been checked the detector heads may be installed in the bases The shorting spring in the base will disengage automatically when the detector head is removed from the base DO NOT remove the shorting spring since it reengages as the detector head is turned into the base completing the circuit CAUTION Tamper resistance Feature Do not use the tamper resistance feature if the XR2 removal too...

Страница 4: ... 800 SENSOR2 736 7672 for a Return Authorization number send defective units postage prepaid to System Sensor Repair Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be defective because of damage unreasonable use modification...

Отзывы: