GST200-2 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 5
Nexans NX 200 and 200 Plus (LPCB tested)
Prysmian FP 200 and 200 Gold
Draka Firetuf and Firetuf Plus
And all LPCB approved Fire cables
Recommended Cable Length
≤
1000m
2.3.2 RS232 Communication Loop
RS232 communication loop is connected with a PC for running GstGMC2.0 Graphic
Monitor Center (GMC) system PC through a DB9 port.
Recommended Wiring: Standard RS-232 interface. The 2
nd
pin (for sending data), the
3
rd
pin (for receiving data), and the 5
th
pin (ground) are connected with PC through
three-core shield cable.
Note: Wire length should be less than 15m; the screening layer and computer’s
enclosure should be earthed.
2.4 Detection Loop Parameters
LOOP OUT (
+
,
-
):
Polarized signal cable from the FACP connecting up to 235
addressable devices.
LOOP IN (
+
,
-
):
Polarized signal cable returning to the FACP.
LOOP2 ZO (
+
,
-
):
Polarized signal cable from the 2
nd
loop of the FACP connecting
up to 242 addressable devices.
LOOP2 ZI (
+
,
-
):
Polarized signal cable from the 2
nd
loop returning to the FACP.
Output Voltage: 21V
~
27V pulse
Output Current: 0mA
~
300mA
Type of Loop: Class A loop
Recommended Wiring (subject to local installation codes):
GST fire cable
Vencroft Gold and Platignum
Nexans NX 200 and 200 Plus (LPCB tested)
Prysmian FP 200 and 200 Gold
Draka Firetuf and Firetuf Plus
And all LPCB approved Fire cables.
Recommended Cable Length
≤
1000m
2.5 Output Loop Parameters
Recommended Wiring (subject to local installation codes):
GST fire cable
Vencroft Gold and Platignum
Nexans NX 200 and 200 Plus (LPCB tested)
Prysmian FP 200 and 200 Gold
Draka Firetuf and Firetuf Plus
And all LPCB approved Fire cables
Recommended cable length
≤
1000m
2.5.1 FIRE ALARM OUTPUT (+, -)
Содержание GST200-2
Страница 1: ......