GST200-2 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 46
Selecting “2. C&E Outputs” on the screen of Fig. 6-46 will set Sounder A on loop
interface board and F.P.E. and the zonal sounder to output by C&E.
The above Default Output does not take effect.
Sounder A, zonal Sounder and F.P.E need to be edited into C&E equation.
Sounder A, zonal Sounder and F.P.E are started according to C&E.
Note:
1
If you have set the “Delay Mode” in Section 6.3.4.4 to “Disable”, the delay time set
here will not take effect.
2
Under no conditions will F.P.E output be delayed.
6.4.5.2 PAS Delay Time Setup
Entering 2 in the screen of Fig. 6-45 will enter the screen for setting up PAS delay time,
as in Fig. 6-47.
Fig. 6-47
When the “PAS Mode” in Section 6.3.5.4 is set to “Enable”, the FACP will enter the first
stage of delay on receiving a fire alarm. Pressing
ACK/MUTE
at this time, the FACP will
enter the second stage of delay. The delay time for the second stage can be set in the
screen shown in Fig. 6-47 as described in Section 6.3.5.4.
6.4.5.3 Resounding Loop Sounders
Choosing “3” on the screen of Fig. 6-45 will enter the screen for resounding loop
sounders, as in Fig. 6-48.
Fig. 6-48
6.4.5.3.1 Resounding Sounders of Other Zones
Choosing “1” on the screen of Fig. 6-48, the silenced sounders of all zones will be
resounded on a new fire alarm from any zone.
6.4.5.3.2 Resounding Sounders of the Same Zone
Choosing “2” on the screen of Fig. 6-48, a new fire alarm will enable to resound
sounders from the same zone. Sounders of other zones will not be resounded.
*PAS Delay Time*
Please Input 000
Range: 000-180
*Re-Sound Configure*
1 Another Zone
2 Self Zone