GST200-2 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 52
Appendix 2 Internal Fault Description
No.
Problems
Description
Causes
1
AC Power
AC power fault
No AC power
2
Bat Fault
Battery fault
No battery or low voltage
3
BATHighZ
Battery high
resistance
Battery aging or loose connection.
4
Charger
Charger fault
Charger circuit damaged.
5
Ground. F
Ground fault
Output loop connects to the ground.
6
F.P.E.
F.P.E. output loop
fault
F.P.E. output circuit opens, shorts or the
end-of-resistor is not connected.
7
Sounder A
Sounder output
loop fault
Souder output loop opens, shorts or the
end of line resistor is not connected.
8
Output1
Alarm output fault
Alarm output circuit opens, shorts or
the end of line resistor is not
connected.
9
PowerBox
Power box fault
Power damaged or can
’t communicate
with main board.
10
Loop1FAIL
Class A Loop 1
fault
Class A loop 1 opens or shorts.
11
Loop2FAIL
Class A Loop 2
fault
Class A loop 2 opens or shorts.
12
Loop2 Card
Loop board 2 fault
Loop board 2 damaged or cannot
communicate with main board.
13
Key Fault
Key fault
CPU for keys damaged or can
’t
communicate with main board.
14
Access
ZCP fault
Zone indication panel damaged or
cannot communicate with main board.
15
ProtBoard
Loop interface
board fault
The board damaged or cannot
communicate with main board.
16
CRT Board
CRT board fault
CRT board damaged or cannot
communicate with main board.
17
Net Card
Network card fault
The card damaged or can
’t
communicate with main board.
18
Repeater
Panel repeater fault The repeater damaged or can
’t
communicate with main board.