GST200-2 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 40
displays pre-alarm message, indicating the position of the alarm and the remaining
delay time.
During the 15-second delay time, if
ACK/MUTE
is pressed, the alarm sound will
stop, and the delay time will be increased by PAS DELAY (0-180s) setup.
After the delay of any stage expires, the pre-alarm will change to fire alarm and fire
protection devices in the system will be started.
During any stage of delay, if there is another detector of the same zone or any
manual call point in the system alarms, the delay will be stopped, the pre-alarm will
be changed to fire alarm, and fire protection devices in the system will be started.
During the delay time, pressing
RESET
will clear the pre-alarm and PAS delay.
6.3.5.5 Manual Start of Loop Device
Entering 5 in the screen of Fig. 6-24 will enter the screen for manual start of system
devices, as shown in Fig. 6-29. The FACP provides two modes, starting a single device
and starting multiple devices. The method of operation and the use of “*” is the same as
disablement.
Fig. 6-29
6.3.5.6 Manual Stop of Loop Devices
Entering 6 in the screen of Fig. 6-24 will enter the screen for manual stop of loop devices.
The method for stopping a device is the same as starting a device.
Fig. 6-30
6.3.6 Device Start/Stop through ZCP
According to definition of the ZCP, press the key corresponding to a device, and input
the requested password, you can start the device. Corresponding command LED of the
key is lit. Press the key and input password again, you can stop the device, and the
command LED turns off.
6.3.7 Test Mode Setup
Start-up
Z000 C000 T00 NoDefine
Stop EQ
Z000 C000 T00 NoDefine