Input “3” on the screen in Fig. 6-35, the screen shown in Fig. 6-41 will be displayed.
Fig. 6-41
In the above screen,
You can set the panel’s network address by entering number 1, as shown in Fig.
6-42.
Fig. 6-42
You can set the panel to display network message or not by entering number 2, as
shown in Fig. 6-43.
Fig. 6-43
6.4.4 Setting up Beginning Zone Number
Pressing “4” on the screen shown in Fig. 6-35, you can set beginning zone number of
the FACP in network. Duplicate zone number should be avoided. The screen is shown
in Fig. 6-44. Entering the number of zones in the network on highlighted position and
pressing
ENTER
, the zone numbers of the FACP will start from this number. For
example, if the beginning number is 003, then the FACP zone number will be 003, 004,
005….in sequence.
*NETWORK SETUP*
1. NET Local Address
2. NET Event Display
*Net Local Address*
Please Input: 01
Range 1-32
*Display Mode*
1 Disable
2 Enable