GST200-2 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 36
Fig. 6-17
Entering 1-digit loop number (1 or 2) and 3-digit point number (any number between 1 to
242), and then pressing
ENTER
will disable the selected device.
Disabling all loop sounders
Entering number “3” in the screen of Fig. 6-15 will enter the screen for disabling all loop
sounders, as shown in Fig. 6-18.
Fig. 6-18
Pressing
ENTER
on prompt will confirm the operation and disable all loop sounders.
Disabling a device by user code
Enter number “4” in the screen of Fig. 6-15 will enter the screen for disabling a device by
user code, as shown in Fig. 6-19.
Fig. 6-19
Enter 3-
digit zone number or “*” at the cursor position after letter “Z”.
Enter 3-
digit device code or “*” at the cursor position after letter “C”.
Enter 2-digit device t
ype or “*” at the cursor position after letter “T”.
Example 1, in order to disable devices with type number 001 of Zone No.1, you need to
input in sequence the zone number 001, device number 001 and device type 03.
Example 2, in order to disable all alarm devices with type number 01
~
11 of Zone No.1,
you need to input in sequence the zone number 001, device code *** and device type **.
Please note that the asterisk mark “**”is not allowed for the type number of action
devices with type number 12
~
65.
Disabling a point
Loop: 1 Point: 000
Disable
Z000 C000 T00 NoDefine
Press ENTER Disabling
All Loop Sounder