GST200-2 Intelligent Fire Alarm Control Panel                

 

Installation and Operation Manual

 

  

                                                  

  

 

 

Page 1  

Installation Precautions 

Adherence to the following will aid in problem-free installation with long-term reliability: 

  Do not attempt to install, service, or operate this unit until this manual is read and 

understood.

 

  This  equipment  must  be  installed  in  accordance  with  these  instructions  and  the 

appropriate  national,  regional  and  local  regulations  specific  to  the  country  and 

location  of  the  installation.  Consult  with  the  appropriate  Authority  Having 

Jurisdiction (AHJ) for confirmation of the requirements.

 

  GST200-2 Fire Alarm Control Panel (FACP) shall only be installed and serviced by 

trained specialist. 

  Disconnect  all  sources  of  power  before  servicing.  Control  unit  and  associated 

equipment  may  be  damaged  by  removing  and/or  inserting  cards,  modules,  or 

interconnecting cables while the unit is energized.  

  Remove all electronic assemblies prior to any drilling, filing, reaming, or punching 

of  the  enclosure.  When  possible,  make  all  cable  entries  from  the  sides  or  rear. 

Before  making  modifications,  verify  that  they  will  not  interfere  with  battery, 

transformer, and printed circuit board location. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание GST200-2

Страница 1: ......

Страница 2: ...truction 7 3 1 1 Display Area 7 3 1 2 Description of LEDs 8 3 1 3 Description of Keys 9 3 1 4 Zone Indication and Manual Interventional Panel ZCP 10 3 2 Components 11 3 2 1 Standard Components 11 3 2 2 Optional Units 11 3 3 Peripheral Devices 13 3 3 1 A Series of Intelligent Fire Detectors 13 3 3 2 Modules 13 3 3 3 Loop Isolator 13 3 3 4 Manual Call Points 13 3 3 5 Sounder Strobes 13 3 3 6 Repeate...

Страница 3: ... 2 Browsing messages 28 6 2 3 Silencing the panel 34 6 3 Instructions for Operator Operator Password Required 34 6 3 1 Resetting the system 34 6 3 2 Alarm Silence 34 6 3 3 Evacuation 34 6 3 4 Disable Enable 34 6 3 5 User Mode 38 6 3 6 Device Start Stop through ZCP 40 6 3 7 Test Mode Setup 40 6 4 Instructions for System Administrator Manager Password Required 42 6 4 1 Modifying System Time 42 6 4 2...

Страница 4: ...tion Consult with the appropriate Authority Having Jurisdiction AHJ for confirmation of the requirements GST200 2 Fire Alarm Control Panel FACP shall only be installed and serviced by trained specialist Disconnect all sources of power before servicing Control unit and associated equipment may be damaged by removing and or inserting cards modules or interconnecting cables while the unit is energize...

Страница 5: ... Output to fire alarm devices 7 8 Outputs to fire protection equipment 7 10 The power supply of GST200 2 FACP complies with EN 54 4 requirements AC DC 100W Power Supply Functions EN 54 4 Clause Power supply from the main power source 5 1 Power supply from the standby power source battery 5 2 Charger 5 3 Faults 5 4 In addition to functions required by EN 54 2 the panel supports a number of ancillar...

Страница 6: ...54 5 photoelectric smoke detector I 9102 complying with EN 54 7 intelligent manual call point I 9202 complying with EN 54 11 intelligent reflective beam detector I 9105R complying with EN 54 12 input and output module I 9300 I 9301 complying with EN 54 18 and loop isolator C 9503 complying with EN 54 17 The LCD can display 8 lines in total and 18 characters each line assisting the 15 LEDs in displ...

Страница 7: ...model of battery Power Sonic PG12V21 Maximum Internal Resistance 1Ω Quiescent Current under Full loaded Condition 0 75A Maximum Battery Operating Current 2 82A Recommended Wiring subject to local installation codes GST fire cable Vencroft Gold and Platignum Nexans NX 200 and 200 Plus LPCB tested Prysmian FP 200 and 200 Gold Draka Firetuf and Firetuf Plus And all LPCB approved Fire cables 2 3 Commu...

Страница 8: ...nal cable from the FACP connecting up to 235 addressable devices LOOP IN Polarized signal cable returning to the FACP LOOP2 ZO Polarized signal cable from the 2nd loop of the FACP connecting up to 242 addressable devices LOOP2 ZI Polarized signal cable from the 2nd loop returning to the FACP Output Voltage 21V 27V pulse Output Current 0mA 300mA Type of Loop Class A loop Recommended Wiring subject ...

Страница 9: ...istor 4 7kΩ 2 5 2 F P E OUTPUT Output Voltage 21VDC 27VDC Output Current 0mA 500mA End of Line Resistor 4 7kΩ 2 5 3 SOUNDER CIRCUIT OUTPUT Output Voltage 21VDC 27VDC Output Current 0mA 500mA End of Line Resistor 4 7kΩ 2 5 4 FAULT OUTPUT NC COM NO Contact Capacity 24VDC 1 0A In fault state NC and COM open NO and COM close 2 6 Dimensions 420mm 580mm 202mm ...

Страница 10: ...tructure are shown in Fig 3 1 and 3 2 Fig 3 1 1 Clock 2 LCD 3 Printer panel 4 Zone indication and manual intervention panel ZCP 5 Keypad 6 LED 7 Optional units Fireman s Control Panel FCP Fig 3 2 1 Display control 2 Zone indication and manual intervention panel ZCP 3 Printer 4 Optional units FCP fireman s control panel 5 Speaker 6 Power supply 7 Loop interface board 8 Transformer 9 PSU filter 10 L...

Страница 11: ...goes out when test mode is canceled POWER ON Green It illuminates when the mains power or battery is normal SYSTEM FAULT Yellow It illuminates if the program encounters a dead halt or the system cannot work normally After the fault condition is removed only by pressing RESET can system fault be cleared and this LED goes out POWER FAULT Yellow It illuminates when the mains power battery or charger ...

Страница 12: ...ighting the EVACUATE LED This key requires operator password RESET For clearing all alarm messages all detector alarms and all outputs in order to reset the FACP to normal state This key requires operator password BROWSE Pressing this key will enter device browsing screen to browse devices by loop by zone or by group to check zones in test to browse definition of communication devices to browse de...

Страница 13: ...ent messages or moving the cursor when entering text For moving the cursor up or down For entering the wild card representing numbers 0 9 0 9 For entering numbers 3 1 4 Zone Indication and Manual Interventional Panel ZCP Appearance of the ZCP is shown in Fig 3 4 Fig 3 4 On the ZCP each unit consists of a key two indicators and a label The key is for start stop control Device labels can be stuck on...

Страница 14: ... provides power to the main board loop interface board and printer Its backup feature ensures that devices registered during commission will not be lost in case of power fault Display area This part is used to indicate and display different status of the system and enables relative operations through keypad browsing programming printing and etc Zone indication and manual intervention panel ZCP The...

Страница 15: ...3 red It illuminates when communicating with the main board Communication card GST200 2 Intelligent Fire Alarm Control Panel FACP provides a multi functional communication port connecting with network cards to realize networking among GST series FACPs to form urban fire alarm supervisory network through public telephone network and to fulfill graphic supervision by connecting with Graphic Monitor ...

Страница 16: ...e detectors 3 3 2 Modules GST200 2 can connect with I 9300 Addressable Input Module and I 9301 Addressable Single I O Module I 9300 module is used for receiving normally open digital signal from fire protection devices and transmitting the signal back to the fire alarm control panel I 9301 module is for connecting fire protection devices that need to be controlled by the FACP such as smoke valve f...

Страница 17: ...h a microprocessor When one or more detectors alarm fire the repeater panel can display the location and alarm message of the detectors with audible and optical signals Through communication loops it can be connected with FACPs disposing and displaying the data from the FACPs When monitoring several floors or several zones with one fire alarm control panel a repeater panel on each floor or in each...

Страница 18: ...cording to packing list The main items to be examined are installation and operation manual keys to the FACP etc Check Internal Components and Interconnection of the FACP All internal parts have been connected including optional units ordered before the FACP leaves the factory Therefore you can mainly check the zone indication and manual intervention panel and power supply and the connection among...

Страница 19: ...by one Check if the LEDs showing the device state on ZCP are illuminated in turn Check if the speaker can give loud alarm sounds 4 4 Connections of Peripheral Devices 4 4 1 Connection of Mains Power GST200 2 Fire Alarm Control Panel receives power from a 220V 230VAC 50Hz 60Hz supply The current flows through a filter to the transformer The transformer converts the input mains voltage to 27VAC The ...

Страница 20: ... the battery terminal P4 P4 P4 Fig 4 2b Note Do not make the final battery connections until the installation is completed 4 4 3 Connection of Peripheral Devices Terminals of loop interface board are shown in Fig 4 3 FAULT OUTPUT NO COM NC LOOP BUS LOOP OUT RS 485 NETWORK B A REPEATER B A F P E OUTPUT LOOP IN FIRE ALARM OUTPUT CLASS CHANGE SOUNDER CIRCUIT OUTPUT Fig 4 3 Caution Do not connect powe...

Страница 21: ...signals when connected circuit is short or open LOOP BUS XT2 XT4 Class A loop can connect with up to 235 addressable devices With loop isolator in Class A loop the detector protected by loop isolator is not missing when there is short or open circuit In this case the FACP reports loop fault RS 485 XT11 XT12 To be connected with repeater panel and FACP earth X8 This terminal is for checking earth f...

Страница 22: ...nd add the resistor to the end of the line NOTE F P E are polarity sensitive Note polarity in connection The maximum current of the circuit depends on the number of F P E Do not overload 4 4 3 3 Connection of FIRE ALARM OUTPUT FIRE ALARM OUTPUT is shown in Fig 4 6 Fig 4 6 A 4 7kΩ resistor is connected at the FIRE ALARM OUTPUT XT5 as factory default Please remove it and keep it well before connecti...

Страница 23: ...een loops and ground which should be more than 20MΩ Measure the load of detection loops which should be more than 1kΩ The resistance between cables of FIRE ALARM OUTPUT SOUNDER CIRCUIT OUTPUT and F P E OUTPUT should be equal to the end of line resistance 4 5 2 Device Registration Press SYSTEM and input commission password Then press ENTER to go to system setting menu Then press ESC to exit system ...

Страница 24: ...ining Tool through a PC and download the definitions to the FACP Refer to GstDef2 1 Defining Tool User s Manual for detailed operation 4 7 Field Device Commission After connection definition and download of device and C E equations you can power up the FACP and start commission The following steps are for reference 1 Complete the labels of ZCP 2 Test all the detectors and make sure their positions...

Страница 25: ... information 5 1 Normal Information The normal display is shown in Fig 5 1 which means the system is in working state Then only POWER ON LED lights Fig 5 1 Fig 5 2 shows the system is in normal operation but with disabled devices Pressing VIEW DISABLE can browse these devices Fig 5 2 5 2 Fire Alarm 5 2 1 Fire Alarm Screen FIRE LED is lit when there is fire alarm signal Speaker of the FACP sounds f...

Страница 26: ... shown in Fig 5 4 Fig 5 4 001 0f 006 FIRE 05 25 There are six devices with fire alarm signals and this is the first Z001 L1 N030MCP The number of zone with fire alarm and type and address of the device in fire alarm Device 30 Description of device in fire alarm Last Fire Zone 003 Number of the zone where the last fire alarm occurs Z 003 Device 066 Description of zone and device of the last fire al...

Страница 27: ...enerates fault sound Fault relay outputs System fault The panel would report system fault if its control CPU and circuits is in fault and the panel cannot work normally It lights the COMMON FAULT and SYSTEM FAULT LED There is no display on the LCD The panel generates continuous alarm sound The panel cannot monitor fire alarm The keypad cannot be used If system fault indication remains for less tha...

Страница 28: ...5 5 in zone display mode and as in Fig 5 6 in loop display mode Fig 5 5 001 0f 002 FAULT10 18 There are two zones reporting fault and this is the first fault message Zone 003 floor3 The number description of the zone with fault message 001 012 There are 12 devices in the zone totally and one of them reports fault Office3 Description of the device with the fault Fig 5 6 001 0f 004 FAULT10 18 There ...

Страница 29: ...les for Message Display If there are multiple messages in the system they will be displayed in the following order fire alarm fault action disable 1 The earliest fire alarm is displayed in priority The latest fault action disabled message is displayed in priority 2 There are zone and loop display modes for fire alarm fault and disabled messages Action message only has loop display mode 3 In any di...

Страница 30: ...e cursor to modify any character Pressing TAB the highlight moves to the next position and returns to the first after the last position Wherever the cursor is Pressing ENTER key all the input data will be saved If there is no keypad operation for over 1 minute the system will exit present state without saving the input data 6 1 3 Unlocking and Locking the Keypad Unlocking the Keypad The FACP is lo...

Страница 31: ...n one piece of message The current information is highlighted when there is more than one piece of message on the LCD You can view details of this item by pressing ENTER or exit by pressing ESC When the printer is set as All History mode pressing ENTER while browsing can print the current displayed message 6 2 2 3 Browse Pressing BROWSE the system enters the browsing screen as shown in Fig 6 3 Fig...

Страница 32: ...ne number with starting zone added total number of devices is 4 Zone 001 office1 Zone number and location NO 001 Optical Device address and type Sensitivity Nominal Device properties Office1 Device position Entering number 3 to choose 3 Group Devices will enter the screen for browsing devices by group as shown in Fig 6 6 Browse Sum 012 L1N001 Optical L1N002 Optical L1N003 Optical L1N004 Sounder Br...

Страница 33: ... 6 7 Sum 002 Total number of zones in test Zone 01 office1 Zone 1 is in test mode Zone description is office1 Zone 05 office5 Zone 5 is in test mode Zone description is office5 Entering number 5 to choose 5 COM Devices will enter the screen for browsing network FACPs and repeater panels Entering number 6 to choose 6 Access will enter the screen for browsing ZCP key definition as in Fig 6 8 Browse ...

Страница 34: ...A condition is composed of the following items General Condition A device can be activated if its zone number code and device type are correct Special Condition Both zone number and device type can be defined If events with the same zone number and device type reach a defined number this special condition comes into effect Asterisk wildcard represents any number used in ENTER Browse C E Sum 003 C ...

Страница 35: ...Date and time of the event Zone Name Zone number zone name 121 Optical Device address and type 6 2 2 5 Browsing fault messages You can view fault messages by pressing VIEW FAULT when the screen is displaying non fault messages The display varies by the type of fault messages Please refer to Section 5 3 6 2 2 6 Browsing disable messages You can view disable messages by pressing VIEW DISABLE when th...

Страница 36: ...first zone Zone 005 Z 005 Zone number and description message of the disabled zone 029 029 All 29 devices of the current zone are disabled Zone Fully Disabled Current zone are completely disabled Fig 6 13 002 of 002 Disable 12 01 There are devices from 2 zones that are disabled and this is the second zone Zone 006 Z 006 Zone number and description message of the disabled zone 016 030 There are 16 ...

Страница 37: ...will re sound on receiving new alarms SILENCE indicator will go out when RESET key is pressed for reset when EVAC key is pressed for evacuation or when system sounders gives new alarm sound 6 3 3 Evacuation Pressing EVAC key can start all system sounders and light EVAC LED until SILENCE or RESET key is pressed After EVAC key is pressed the LCD will display EVAC IN SYSTEM Press ENTER confirm Pressi...

Страница 38: ...ble a device by user code Fig 6 15 Disabling a zone Entering number 1 in the screen of Fig 6 15 will enter disable screen as shown in Fig 6 16 Fig 6 16 Entering 3 digit zone number and Pressing ENTER key to confirm will disable all devices of the zone Disabling a point device Entering number 2 in the screen of Fig 6 15 will enter the screen for disabling a single device as shown in Fig 6 17 Disabl...

Страница 39: ... a device by user code as shown in Fig 6 19 Fig 6 19 Enter 3 digit zone number or at the cursor position after letter Z Enter 3 digit device code or at the cursor position after letter C Enter 2 digit device type or at the cursor position after letter T Example 1 in order to disable devices with type number 001 of Zone No 1 you need to input in sequence the zone number 001 device number 001 and de...

Страница 40: ...larm output as shown in Fig 6 21 Fig 6 21 In this screen the SOUNDER CIRCUIT OUTPUT and FPE OUTPUT on the loop interface board can be disabled or enabled 6 3 4 4 Disabling Enabling Delays Inputting number 4 in the screen shown in Fig 6 14 can enter the screen of disabling enabling delays as shown in Fig 6 22 Fig 6 22 In the above screen you can operate as follows Selecting number 1 will disable al...

Страница 41: ...will delete the disabled information from network FACP 6 3 5 User Mode Pressing MODE key can enter user mode setup screen as shown in Fig 6 24 Fig 6 24 In this screen the user can setup the screen contrast display mode printing mode and pre alarm mode and can also start or stop devices 6 3 5 1 LCD Contrast Setup Entering 1 in Fig 6 24 will enter the screen for setting up LCD contrast as shown in F...

Страница 42: ...ed Entering number 2 means only printing fire alarm message Entering number 3 means printing the currently viewed message when checking history records 6 3 5 4 Positive Alarm Sequence PAS Setup Entering 4 in the screen of Fig 6 24 will enter the screen for setting up pre alarm screen as shown in Fig 6 28 Fig 6 28 If the panel is set to PAS mode enabled On receiving the first fire alarm from a dete...

Страница 43: ...T will clear the pre alarm and PAS delay 6 3 5 5 Manual Start of Loop Device Entering 5 in the screen of Fig 6 24 will enter the screen for manual start of system devices as shown in Fig 6 29 The FACP provides two modes starting a single device and starting multiple devices The method of operation and the use of is the same as disablement Fig 6 29 6 3 5 6 Manual Stop of Loop Devices Entering 6 in ...

Страница 44: ... Single zone Testing Setup Entering 2 in the screen of Fig 6 30 will enter the screen for setting up single zone testing as shown in Fig 6 32 Fig 6 32 Entering the zone to test in this screen and pressing ENTER to confirm the zone will enter test mode and the TEST MODE indicator will illuminate 6 3 7 3 Exiting Single zone Testing Mode Entering 3 in the screen of Fig 6 31 will enter the screen for ...

Страница 45: ... Fig 6 35 Fig 6 35 6 4 1 Modifying System Time Entering 1 in the screen of Fig 6 35 the system enters Time Date setting screen as shown in Fig 6 36 After Entering time at highlighted position and press TAB then the next cell is highlighted Pressing ENTER will save the modification Fig 6 36 6 4 2 Modifying Password Entering 2 on the screen in Fig 6 35 the system enters the window for password modif...

Страница 46: ...rom 0 9 is input the LCD will display the screen shown in Fig 6 39 requesting to confirm password Fig 6 39 Entering the new password again if the two passwords are the same the LCD will display the window shown in Fig 6 40 meaning the modification is successful Fig 6 40 6 4 3 Network Setup Password Change 1 Operator Password 2 Manager Password Modify Password Input password Modify Password Confirm...

Страница 47: ... 6 43 6 4 4 Setting up Beginning Zone Number Pressing 4 on the screen shown in Fig 6 35 you can set beginning zone number of the FACP in network Duplicate zone number should be avoided The screen is shown in Fig 6 44 Entering the number of zones in the network on highlighted position and pressing ENTER the zone numbers of the FACP will start from this number For example if the beginning number is ...

Страница 48: ...ecting 1 Default Outputs in the screen of Fig 6 46 will set SOUNDER CIRCUIT OUTPUT Sounder A on loop interface board and F P E OUTPUT F P E and the zonal sounder to default output That is if any fire alarm comes If you have set the Delay Mode in Section 6 3 4 4 to Disable Sounder A zonal sounder and F P E will be automatically started If you have set the Delay Mode in Section 6 3 4 4 to Enable Sou...

Страница 49: ...When the PAS Mode in Section 6 3 5 4 is set to Enable the FACP will enter the first stage of delay on receiving a fire alarm Pressing ACK MUTE at this time the FACP will enter the second stage of delay The delay time for the second stage can be set in the screen shown in Fig 6 47 as described in Section 6 3 5 4 6 4 5 3 Resounding Loop Sounders Choosing 3 on the screen of Fig 6 45 will enter the sc...

Страница 50: ... shown in Fig 6 35 can initialize system data 6 4 7 Viewing Supervisory Data of Addressable Devices Entering 7 on the screen shown in Fig 6 35 will enter the window shown in Fig 6 49 Entering the equipment number and the order number can view the supervisory value of addressable devices Fig 6 49 GST CO LTD Equipment Num 001 Order Number 002 ...

Страница 51: ...escent current when the FACP is with no load ILmax 0 3A x 2 0 6A is the maximum loop current for 2 detection loops IFout 0 5A 3 1 5A which is the alarm output current The FACP provides 3 fire alarm outputs output current of each is 0 5A T1 is the monitoring time when the FACP is full loaded which shall be at least 24 hours according to EN 54 4 T2 is the alarm time which shall be at least 30 minute...

Страница 52: ...battery Recommended period for replacing the battery 5 years 25 Recommended manufacturer and model Power Sonic PG12V21 Disposal of used batteries Please properly dispose the used batteries according to your local rules and regulations NOTE RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE 8 2 Replacing the Fuses Table 8 1 Location Mark Rated Value Power filter F7 820 323 F1 2A Delay Po...

Страница 53: ...s 4 Unable to register loop equipment Bus wrong or loose connection Check the loop 5 Unable to register repeater panels Wrong or loose connection of communication cables Check power supply to repeaters and communication wires 6 Cannot print a Print mode is not set b Loose connection with printer c Printer damaged a Set the print mode b Check and connect the printer well c Replace the printer 7 No ...

Страница 54: ... Panel Installation and Operation Manual Page 51 Appendix 1 Internal Connection Diagram To Enclosure 1 Main Board 2 Switch Board 3 LCD 4 Printer 5 Speaker 6 Loop Interface Board 7 Power Board 8 Transformer 9 Power Filter 10 ZCP 11 Loop Board ...

Страница 55: ...rcuit opens shorts or the end of line resistor is not connected 9 PowerBox Power box fault Power damaged or can t communicate with main board 10 Loop1FAIL Class A Loop 1 fault Class A loop 1 opens or shorts 11 Loop2FAIL Class A Loop 2 fault Class A loop 2 opens or shorts 12 Loop2 Card Loop board 2 fault Loop board 2 damaged or cannot communicate with main board 13 Key Fault Key fault CPU for keys ...

Страница 56: ...tor MCP 11 Manual call point VAModule 12 Voice alarm module Sounder 13 Sounder strobe FTModule 14 Fire telephone module HR MCP 15 Hydrant pump HR Pump 16 Hydrant pump SPKR Pmp 17 Sprinkler pump PS SW 18 Stabilized pressure pump Extract 19 Smoker exhauster Presuriz 20 Blower FreshAir 21 Fresh air Damper 22 Fire damp SM Vent 23 Smoke vent AirInlet 24 Air inlet SolValve 25 Solenoid valve SM CURT 26 R...

Страница 57: ...U 44 Power supply unit EM Light 45 Emergency light EscapeLT 46 Escape light GasActiv 47 Gas activation Security 48 Security module ZoneValv 49 Zone valve Cylinder 50 Cylinder DelugePM 51 Deluge pump Undefine 52 Undefined Stop Mod 53 Device stop Silence 54 Mute key SounderA 55 Fire alarm sounder SounderF 56 Fault sounder Loop SW 57 Loop switch CRTFault 58 GMC fault Loop 59 Loop PSU Bat 60 Battery P...

Страница 58: ...d 1 LCD Contrast 2 Browse Mode Zone Mode Loop Mode 3 Print Mode Disable Only Fire All History Pressing PRINT when viewing history records can print out the messages being viewed 4 PAS Positive Alarm Sequence Setup 1 Disable 2 Enable 5 Start Devices manually start 6 Stop Devices manually stop TEST Operator Password required 1 Display Test Self test 2 Each Zone In Test 3 Stop a Zone Test 4 Stop All ...

Страница 59: ...delay SILENCE Silencing all sounders in the system Operator Password Required EVAC Start all sounder in the system for evacuation Operator Password Required LOCK Locking keypad Turning pages ESC Canceling or exiting operation menu or enabling the FACP to displaying information of the highest priority ENTER Confirmation an input Shifting time display mode between month day and hour minute in normal...

Страница 60: ...Gulf Security Technology Co Ltd No 80 Changjiang East Road QETDZ Qinhuangdao Hebei P R China 066004 Tel 86 0 335 8502434 Fax 86 0 335 8502532 service gst fs utc com www gst com cn ...