GST100 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 3
Output Current: 0
~
500mA
Terminal Resistor: 4.7K
2
ALARM OUTPUT (NC,COM, NO)
Contact Capacity: 24VDC @1.0A
In case of a fire alarm or supervisory condition, NC and COM open, NO and
COM close.
3
FAULT OUTPUT (NC, COM, NO)
Contact Capacity: 24VDC @1.0A
In case of a fault condition, NC and COM open, NO and COM close.
2.5 RS485 Communication Loop
A, B: RS485 communication cable, for connecting with up to 32 network fire
alarm control panels and 64 repeater panels.
Recommended Wiring:
GST FireCable ® 2E/1.0 2 core and Earth 1mm
2
CSA
Pirelli Cable Limited FP200 FLEX 2 core and Earth 1mm
2
CSA
2.6 Dimensions
300mm×210mm×91mm