GST100 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 37
2.Address Setup
1.Display Setup
Fig. 8-2
Local address
01
Fig. 8-3
As different system requires different network function, the FACP is designed to be able to
filter network information. In this mode, The FACP displays only its local messages, but
does not display messages from other network panels. The following settings will enable
the filter ability:
Moving the highlight to
“1. Display Setup” in the screen of Fig. 8-2 and pressing
Enter
will
enter the screen as in Fig. 8-4. If
“Enable” is selected, the FACP will display the fire,
supervisory and fault message from the network. If
“Disable” is selected, the FACP will
display its local messages. (
“[*]” refers to the selected option).
Disabled [ ]
Enabled [*]
Fig. 8-4
If this FACP is used as the host panel and set in commission status (refer to Section 7.1),
re-booting it after network address and display mode are set up will automatically update its
network configuration.
8.3.2 Connecting with Repeater Panels
The FACP can connect with up to 64 repeater panels in order to transmit the fire alarm
messages and give audio alarm.
The messages to be transmitted to the repeater panels are the location and code of the
device that alarms the fire, so that the location can be quickly found.
8.4 Display of Network Messages
8.4.1 Network Fault
The FACP will report fault messages as shown in Fig. 8-5 and 8-6 in case there are power
down with network panels and repeater panels, off-normal communication or damaged