GST100 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 2
Chapter 2 Technical Specifications
2.1 Operating Voltage
Input Voltage: 230V AC
+10%
-15%
Frequency: 50Hz
Input Current: 0.2A
Fuse: 2A
Recommended Wiring: 1.5mm
2
or above shield cable, complying with local
installation code.
2.2 Standby Batteries
Maximum Charge Current: 0.3A±0.05A
Maximum Charge Voltage: 27.5V±0.5V
Type: Sealed lead acid batteries
Maximum Battery Capacity: 24V/7Ah
Recommended Wiring:
GST FireCable ® 2E/1.5 2 core and Earth 1.5mm
2
CSA
Pirelli Cable Limited FP200 FLEX 2 core and Earth 1.5mm
2
CSA
2.3 Detecting Loop Parameters
LOOP OUT (+, -): Polarized signal cable from the FACP connecting with up to
128 addressable devices.
LOOP IN (+, -):
Polarized signal cable returning to the FACP.
Type of loop: Class A
Recommended Wiring:
GST FireCable ® 2E/1.0 2 core and Earth 1mm
2
CSA
Pirelli Cable Limited FP200 FLEX 2 core and Earth 1mm
2
CSA
2.4 Output Loop Parameters
Recommended Wiring:
GST FireCable ® 2E/1.0 2 core and Earth 1mm
2
CSA
Pirelli Cable Limited FP200 FLEX 2 core and Earth 1mm
2
CSA
1
SOUNDER OUTPUT (R+, R-)
Output Voltage: 21VDC
~
27VDC