GST100 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 6
OUTPUT
Green sounder (R+, R-) outputs.
②
Both LED illuminate when
SOUNDER OUTPUT (R+, R-) is
disabled.
③
Both LED flash when the
SOUNDER OUTPUT (R+, R-) is in
trouble condition.
panel is reset.
②
Both LED go off when the
SOUNDER OUTPUT (R+, R-)
is enabled.
③
Both LED go off when the
trouble condition is cleared.
Disabled
Yellow Turns on when there is a connected
device or an output or the delay
mode is disabled.
Enable all devices or outputs,
refer to Section 6.5
Fault
Yellow Turns on when a trouble condition is
detected.
Remove the cause of the
trouble.
AC Fault
Yellow Turns on when 230VAC power
supply is down or damaged.
Remove the cause of the
trouble.
Battery Fault
Yellow Turns on when the standby battery
is under-voltage or damaged.
Remove the cause of the
trouble.
System Fault Yellow
①
Illuminates when the memory of
the panel is in trouble.
②
Flashes when system program
cannot be executed.
Remove the cause of the
trouble.
Power
Healthy
Green Illuminates when power supply
works normally.
Maintenance
Yellow Illuminates when a detector reports
dirty.
Clean the detector and then
reset the panel.
Mute
Yellow Illuminates
when
the
panel
’s
speaker is turned off.
Verify the cause of the event
and reset the control panel.
Note: If there is new fire alarm,
the speaker will be re-activated
and this LED will go off.
Silence
Yellow Illuminates when the sounders are
silenced or when the SOUNDER
OUTPUT (R+, R-) is disabled.
Verify the cause of the event
and reset the control panel.
Note: If there is new fire alarm
or the
Silence
key is pressed
again,
the
sounder
or
SOUNDER OUTPUT will be
re-activated and this LED goes
off.
Delay
Yellow Illuminates when there is a sounder
or an output in delay mode.
Verify the cause of the event.
This LED goes off when the
panel is reset or the delay time
expires.
Zonal LED
Fire
Red
Turns on when a device of the zone
alarms fire.
Verify the cause of the event
and then reset the FACP.
Flt/Disabled
Yellow
①
Flashes if a device of the zone is
in trouble condition.
②
Illuminates if all devices of the
zone are disabled.
①
Remove the cause of the
trouble.
②
Enable all devices of the
zone.
Содержание GST100