GST100 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 30
Chapter 7 System Operator
’s Guide
System configuration can be modified by pressing
System
(Fig. 7-1) where Level 2 password
is required.
The first screen
1.Definition
2.Register
The second screen
4.Device Modify
3.Password
The third screen
5.Monitoring
Fig. 7-1
7.1 System Status Setup
Pressing System and entering Level 2 password will enter system setup menu, and there will
be a
“-“ at the right bottom of the screen showing the system is in commission status. About
2 minutes later the
“-“ will disappear and the screen changes to monitor status. Resetting
the panel can also change the system from commission to monitor status.
Commission Status is used in project commission or the system configuration needs to be
modified (such as the number of loop devices or network equipment). Registering devices
in this status will update registration information and network configuration.
Monitor Status is the normal status after completion of project commission. Under this
status registration information and network configuration cannot be updated.
7.2 Device Definition
Selecting
“1. Definition” under the screen shown in Fig. 7-1 will enter the screen of device
definition shown in Fig. 7-2.