GST100 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 18
(2) The speaker gives supervisory sound (fire truck sound). The
Supervisory
LED
illuminates.
(3) The sounder of this zone and the common zone will be triggered.
(4) If supervisory is enabled, the normally open contact of ALARM OUTPUT relay (NO,
COM) is closed, and the normally closed contact (NC, COM) open, the
Fire Output
LED lights red. If SOUNDER OUTPUT is enabled, the R+ and R- contact is closed to
output, and
SOUNDER OUTPUT
LED lights red.
Please refer to Section 6.5.3 for the operation methods to enable the supervisory output and
SOUNDER OUTPUT.
Abno-
rmal
001/002 2-065
15/12 13:26
Abno-
rmal
002/002 3-059
15/12 13:35
Fig. 5-7
5.8 Action Message
When there is a fire alarm and the zonal sounder is activated or the ALARM OUTPUT,
SOUNDER OUTPUT(R+, R-) or FAULT OUTPUT are triggered, the FACP will give the
following action messages:
(1) The LCD displays the action messages as in Fig. 5-8.
(2) The speaker gives action sound (quick police car sound).
(3) Pressing
Silence
can close the sounder and SOUNDER OUTPUT (R+, R-). Pressing
Silence
again can re-start the sounder and SOUNDER OUTPUT(R+, R-).
Acti-
on
001/002 3-039
15/12 08:26
Acti-
on
002/002 -----
15/12 10:30
Fig. 5-8
5.9 Delay Message
The output of the FACP can be delayed. Please refer to Section 6.5.5 for operation of
enabling /disabling the output delay. The delay time can be set under Unser\Delay Setup menu,
please refer to Section 6.6.3.
When an alarm comes while the output delay is enabled and the zonal delay time is not 0, the
FACP will automatically delay the start of the zonal sounder. If the common zone delay time is
not 0, the FACP will automatically delay the start of the common zone sounders. The LCD will
display the delay message shown as in Fig. 5-9. The
Delay
LED illuminates. On expiry of the
delay time, the
Delay
LED goes off, the sounder starts and the FACP gives action messages.