GST100 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 12
Fig. 4-4
4.5 Commission
4.5.1 Connection checking
Check the loop conditions, measure the insulation resistance between the loop and ground,
and inspect loop load, of which the insulation resistance should be more than 20M
Ω , and
loop load more than 1k
Ω . Cross cable resistance is equal to the terminal resistance.
4.5.2 Registering Devices
Press
System
key and input password (system default is no password), then press
Enter
to
access system menu. Then reboot the FACP, it will automatically register system devices,
and check if the number, code and status comply with project design.
The FACP will automatically identify the loop device if it is first registered. The devices can be
assigned into zones by their codes. The user can put number 1-15 into the same zone;
number 16-30 into another zone
…and etc. Devices after No. 120, which are sounders only,
are usually installed in the common zone. In addition, a sounder will be assigned to a zone.
4.5.3 Defining Devices
Zones can be re-assigned according to field situations. The system does not limit the number
and code of devices for each zone. The sounders can be addressed to any number within
1
~
242.
Max. 32 FACP
B
A
Max. 64 repeater panels
B
A
F
A
C
P
R
e
p
e
a
te
r
F
A
C
P
R
e
p
e
a
te
r