GST100 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 19
Delay
001/002 2-115
Time:025
Delay
002/002 -----
Time:035
Fig. 5-9
The messages on the screen mean that there are 2 devices being delayed. The sounder
number 115 in Zone 2 will activate after 25 seconds and SOUNDER OUTPUT (R+. R-) will
activate after 35 seconds. The delay time on the screen will decrease as the time passes.
During the delay period, pressing a manual call point will stop the delay and start the sounders,
ALARM OUTPUT and SOUNDER OUTPUT contact (R+, R-).
5.10 Disable Messages
When there are problems with connected devices, it may be necessary to disable them for
repair, and then enable them after repairing or replacing. When there is a disabled device, the
FACP gives disable message.
(1) The LCD displays disabled messages as in Fig. 5-10.
(2)
Disabled
LED illuminates.
(3) If all devices of a zone are disabled, the zonal
Flt/Disabled
LED illuminates.
Dis-
abled
001/002 2-015
15/12 08:26
Dis-
abled
002/002 1-001
15/12 10:30
Fig. 5-10
During the disabled period, the disabled part doesn
’t work which will affect the system
performance. Please have them repaired or replaced as soon as possible. In the mean time,
more attention shall be paid to the area of the disabled devices to avoid and potential risks.