GST100 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 14
5.2 Rules for Sound Indication
The FACP will sound to indicate fire alarm or fault messages. In case of multiple messages,
the FACP will sound by the following priority:
(1) Fire alarm: fire truck sound
(2) Supervisory: fire truck sound
(3) Action: quick police car sound
(4) Fault: Ambulance sound
Pressing
Mute
can stop the sound of the FACP; In mute state,
Mute
LED illuminates, and the
speaker stops sounding. Pressing
Mute
again, the FACP is still in mute state. It will sound by
priority when new event appears. If new alarm occurs, the
Mute
LED is off, and the
corresponding sound of the alarm will be heard. For instance, if a new fault condition occurs in
mute state, the FACP will generate a fault sound.
5.3 System Normal Message
Fig. 5-2 shows the system normal screen.
15/12 09:45
System Running
Fig. 5-2
5.4 Fire Message
5.4.1 Fire Message Display
GST100 control panel will generate alarm signal in 10 seconds when a detector alarms fire or a
manual call point is pressed.
(1) The LCD displays fire messages shown as Fig. 5-3.
(2) The speaker gives fire alarm sound (fire truck sound). The general
Fire
LED and the
zonal
Fire
LED illuminate.
(3) The sounders in this zone and the common zone are triggered.
(4) When fire output is enabled, the normally open contact of ALARM OUTPUT (NO,
COM) is closed and the normally closed contact (NC, COM) is open. The
Fire Output
LED illuminates. When SOUNDER OUTPUT (R+, R-) is enabled, the R+ and R- are
closed to start output. The
Fire Output
or
SOUNDER OUTPUT
LED lights red.
Please refer to Section 6.5.3 for the operation method to ALARM OUTPUT and
SOUNDER OUTPUT (R+, R-).