GST100 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 22
the device before or after it.
In Fig. 6-5, we can see there are 98 devices on line and the current device No. 232 is in Zone 8
which is a manual call point.
Z-8 Analog
Code: Sum:098
232
Fig. 6-5
For digital detector, there will be a
“->” at the right bottom of the screen, indicating you can
enter the following screen by pressing
Enter
.
Z-5 Digital ->
Code: Sum:098
135
Fig. 6-6
In Fig. 6-6, we can see there are 98 devices on line and the current device No. 135 is in Zone 5
which is a digital smoke detector. Pressing
Enter
, the screen displays as follows:
Clear Air = 021
ALT = 115 Vc = 179
Fig. 6-7
In the above screen, ALT (Alarm Threshold) refer to alarm threshold which is related with the
detector
’s sensitivity. Vc (Current Value) refers to the current sampled value. “Clear Air”
value refers to the initial background light, which is a calibrated value under a reference testing
environment.
6.4.2 Viewing Network FACP
In the screen of Fig. 6-4, moving the highlight to
“2. Net Unit” and pressing
Enter
or using
number key 2, the system will enter the screen of viewing network units which includes the
quantity and number of the FACP in the network.
6.4.3 Viewing Repeater Panels
In the screen of Fig. 6-4, moving the highlight to
“3. Repeater” and pressing
Enter
or using
number key 3, the system will enter the screen of viewing repeater panels which includes the
quantity and number of the repeater panels on line.
6.5 Disabling and Enabling Devices
Pressing
Disable
or
Enable
, the system displays the following: