68 / EN
Heat Pump Monobloc Inverter / User Manual
202202
Heat Pump Space Heater 66
4.4.19.5 E17Diagnosis and analysis
4.4.19.5.1 Diagnosis
E17 occurs when the instantaneous input current peak of the DC bus is over high.
4.4.19.5.2 Possible cause
!
The input power supply is abnormal, and the voltage suddenly decreases to cause the input
current to increase.
!
Inductor on PFC module malfunctioned.
!
Inverter module PCB malfunctioned.
4.4.19.5.3 Analysis and action
Note:
1. For 8/10/12/14/16kw, refer to Figure4-19.6 below for the location of the inductor.
Figure4-19.6
Yes
NO
Yes
NO
E17
Inductor on PFC module malfunctioned?
1
Power supply is abnormal?
Restart the unit once the power
supply has returned to normal
Replace drive PCB
Replace the inductor
Inductor enveloped
by a cover plate