4.4.24 E28Diagnosis, analysis and action
4.4.24.1 Diagnosis
Code E28 will occur when drive PCB receives no data or error data from refrigeration system
PCB in 30 seconds.
4.4.24.2 Possible causes
!
The communication cables with the main control PCB are loose or open.
!
Drive PCB is damaged.
4.4.24.3 Analysis and action
Note:
1. Apply to 14/16kW models, for 8/10/12kW models no separator communication lines.
2. Apply to 14/16kW models, for 8/10/12kW models no separator refrigeration system PCB.
Yes
NO
NO
Yes
Reconnect or replace the
communication cables
Communication cables between
refrigeration system PCB and drive PCB are
loose or open?
1
E28
Replace drive PCB
Replace refrigeration
system PCB
Refrigeration system PCB is damaged?
2