62 / EN
Heat Pump Monobloc Inverter / User Manual
202202
Heat Pump Space Heater 60
4.4.18 E14 diagnosis and analysis
4.4.18.1 Diagnosis
Code E14 indicates heat pump shut down because of the error of low pressure sensor LPS.
4.4.18.2 Possible causes
!
Low pressure sensor is not connected properly
!
Low pressure sensor has malfunctioned.
4.4.18.3 Analysis and action
Low pressure sensor connection on
refrigerant system PCB is loose?
E14
Yes
Ensure the sensors is connected
properly
NO
Low pressure sensor has short-circuit or
malfunctioned?
Yes
Replace the sensor
NO
Replace refrigerant system PCB