79 / EN
Heat Pump Monobloc Inverter / User Manual
77 Heat Pump Space Heater 202202
4.4.26 E22 E32 E33 E35 E37 E38 analysis
These codes mean the controller is performing some kind of specific action; they are neither
error nor failure.
!
E22 will occur if the inverter module is resetting.
!
E32 E33 and E35 will occur if the inverter module is debugging the data.
!
E37 will occur if the compressor frequency is limited because of the input current of the
inverter module.
!
E38 will occur if the compressor frequency is limited because of the input voltage of the
inverter module.
4.4.27 E01/E02/E03/E04/E05/E06/E07/ E08/E09/E10/E14/E28 analysis
Before starting heat pump, if the communication cables with two cores (A and B) between the
control board 1 and the control board 2 are not connected, all these errors above will occur on
the user interface and don’t start heat pump. First of all, you must confirm that the
communication cables (A and B) between these two control boards have been connected
correctly to start heat pump.
E01/E02/E03/E04/E05/E06/E07/
E08/E09/E10/E14/E28
Connect the communication cables between the
control board 1 and the control board 2