73 / EN
Heat Pump Monobloc Inverter / User Manual
71 Heat Pump Space Heater 202202
4.4.20 E19 E24 E27Diagnosis and analysis
4.4.20.1 Diagnosis
!
E19 will occur when PFC module is abnormal.
!
E24 will occur when PFC module temperature is too high.
!
E27 will occur when the circuit of PFC module detecting temperature is abnormal.
4.4.20.2 Possible causes
!
The input power supply is abnormal.
!
Screws on PFC module are loose.
!
Internal PFC circuit detecting the temperature malfunctioned.
!
The radiator on PFC module has poor heat dissipation.
!
PFC module circuit malfunctioned.
!
Inverter module PCB is damaged.
4.4.20.3 Analysis and action
Yes
NO
Yes
NO
Yes
NO
Yes
NO
NO
Yes
Replace drive PCB
E19 E24 E27
Power supply is abnormal?
Restart the unit once power supply
is normal
Screws on PFC module are loose?
The radiator on inverter module PCB has
poor heat dissipation?
Tighten the screw
Ensure good heat dissipation on the
radiator
PFC module circuit malfunctioned?
Internal PFC circuit detecting the
temperature malfunctioned?
Replace drive PCB
Replace drive PCB
Содержание GHP-MM08
Страница 27: ...27 EN Heat Pump Monobloc Inverter User Manual...
Страница 28: ...28 EN Heat Pump Monobloc Inverter User Manual 3 9 2 GHP MM14 GHP MM16...
Страница 29: ...29 EN Heat Pump Monobloc Inverter User Manual...
Страница 72: ...72 EN Heat Pump Monobloc Inverter User Manual Figure 4 19 9 14 16kw...
Страница 83: ...Beko Grundig Deutschland GmbH Rahmannstra e 3 65760 Eschborn www grundig com...