Heat Pump Monobloc Inverter / User Manual
202202
Heat Pump Space Heater 64
4.4.19.4 E15 and E16 diagnosis and analysis
4.4.19.4.1 Diagnosis
The normal DC voltage between terminals P (DC+) and N (DC-) on inverter module PCB is 1.4
time of AC power supply in standby state. The DC voltage is 370V when the fan motor is running.
If the voltage is lower than 180V, the unit displays E15 and shuts down. If the voltage is higher
than 430V, the unit displays E16 and shuts down.
4.4.19.4.2 Possible causes
!
Power supply is abnormal.
!
Relay on the inverter module PCB is open.
!
Drive PCB is damaged.
Figure 4-19.4 Location of DC bus voltage terminals for 8/10/12kW:
Figure 4-19.5 Location of DC bus voltage terminals for 14/16kW: