21 / EN
Heat Pump Monobloc Inverter / User Manual
19 Heat Pump Space Heater 202202
22 Compressor resonance point 1
FR1
0
Hz
0
~
120
1
23 Compressor resonance point 2
FR2
0
Hz
0
~
120
1
24 Compressor resonance point 3
FR3
0
Hz
0
~
120
1
25 Compressor resonance point 4
FR4
0
Hz
0
~
120
1
26
Ambient temperature for
electric heating of water tank
Teh
4
℃
-10
~
40
1
27
Whether automatic
temperature adjustment is
effective
Auto heating
Adjust enable
0
0/1
0-disable
1-enable
1
28
Temperature compensation
high point
Hi_A
5
℃
0
~
20
1
29
Temperature compensation
low point
Lo_A
0
℃
-20
~
0
1
30
Maximum temperature
compensation
A
5
℃
0
~
10
1
31
Whether the high heating
temperature shutdown is
effective
To enable high
temp. heating
shutdown
0
0/1
0-disable
1-enable
1
32
Heating high temperature
shutdown temperature setting
T4h
24
℃
10
~
30
1
33
PWM water pump brand
MPumpTyp
3
/
0-AC pump
1-OMT1
2-Grundfos
3-Wilo
4-OMT2
1
34
Pump running status in heating
standby mode
H-Pump
3
0/1
0-On 1min OFF
3min
1-ON 1min OFF
10min
2-On 2min OFF
15min
3-Always On
1
35
Low temperature stop
compressor temperature
setting
T4L
-30
℃
-40
~
-21
1
36
Pipeline electric heating is
effective or invalid
HD
0
0/1
0-enable
1-disable
1
37
Whether the cooling mode is
effective
Cool on enable
0
0/1
0-enable
1-disable
1
202202
Heat Pump Space Heater 18
3.8 EEPROM Parameter Setting
Press “
M” and “Up” two keys at the same time, and then enter the password “1212” to adjust
EEPROM parameter value. Refer to the table below for the detailed setting.
Item
Name
Code
Default
Unit
Range
Accuracy
1
Air conditioning water
temperature return difference
Ta
2
℃
1
~
5
1
2
Hot water temperature
difference
Tb
5
℃
2
~
15
1
3
Cooling target exhaust
temperature correction
TargetTPc
0
℃
-10
~
15
1
4
Heating superheat
SHh
-1
℃
-5
~
10
1
5
Compressor frequency in
refrigeration test mode
LCF_C
68
Hz
20
~
120
1
6
Compressor frequency in
heating test mode
LCF_H
68
Hz
20
~
120
1
7
Compressor frequency in hot
water test mode
LCF_W
68
Hz
20
~
120
1
8
Cooling test mode EEV opening
EEV_C
250/5
P
(0
~
480)/5
1
9
Heating test mode EEV-1
opening
EEV_H
150/5
P
(0
~
480)/5
1
10
Hot water test mode EEV-1
opening
EEV_W
150/5
P
(0
~
480)/5
1
11
Defrost entry temperature
DST
-5
℃
-15
~
0
1
12
Defrost enters temperature
difference
Dt
12
℃
0
~
15
1
13
Judgment time of first defrost
T1
40
min
20
~
90
1
14 Defrosting process EEV opening
Opl
480/5
P
(0
~
480)/5
1
15 Defrost compressor frequency
FD
12
Hz
30
~
120
1
16 Maximum operating frequency
Fmax
85
Hz
30
~
120
1
17
Power-off memory
PR
1
0/1
0-disable
1-enable
/
18
Silent mode frequency limit
Fs
55
Hz
30
~
120
1
19
Sterilization set temperature
Tx
65
℃
55
~
75
1
20
Disinfection duration time
Td
30
Min
20
~
120
1
21
Run mode priority
Mp
0
0/1/2
0-DHW
1-Space AC
2-Preempt
/
Содержание GHP-MM08
Страница 27: ...27 EN Heat Pump Monobloc Inverter User Manual...
Страница 28: ...28 EN Heat Pump Monobloc Inverter User Manual 3 9 2 GHP MM14 GHP MM16...
Страница 29: ...29 EN Heat Pump Monobloc Inverter User Manual...
Страница 72: ...72 EN Heat Pump Monobloc Inverter User Manual Figure 4 19 9 14 16kw...
Страница 83: ...Beko Grundig Deutschland GmbH Rahmannstra e 3 65760 Eschborn www grundig com...