4.4.19.6 E18 E23 E29 E30 Diagnosis and analysis
4.4.19.6.1 Diagnosis
!
Code E18 will occur when IPM module is abnormal.
!
Code E23 will occur when the instantaneous peak current of any phase of three phases the
compressor U, V and W is over high.
!
Code E29 will occur when the internal circuit of IPM detecting temperature is abnormal.
!
Code E30 will occur when IPM module overheats.
4.4.19.6.2 Possible cause
!
The compressor phase sequence is incorrectly connected.
!
Too much refrigerant liquid flooded into the compressor.
!
The compressor malfunctioned.
!
Screws on the inverter module are loose.
!
The radiator on inverter module PCB has poor heat dissipation.
!
The inverter module PCB malfunctioned.