Heat Pump Space Heater 42
Notes:
1. The blockage of high pressure side of the refrigerant system will lead to higher discharge
temperature, higher discharge pressure and lower suction pipe pressure.
2. In heating and DHW mode check water side heat exchanger, water piping, circulator
pumps and water flow switch for dirt and blockages. In cooling mode check air side heat
exchanger, the fan and air outlets for dirt and blockages.
3. Check the outlet pressure of the water system. If the pressure is lower than 1 bar, water
flow rate is insufficient.