37
4.2.4 Measurement parameters
In case of limit value monitoring, the GENO-softwatch Komfort must
be parameterised for total hardness.
Note:
The respective limit value is determined by the indicator used.
For available indicators, please refer to chapter B-3.
S6 S7 S8 Parameter
OFF OFF OFF
Total hardness
4.2.5 Limit value monitoring
In general, an alarm will be emitted if the limit value is exceeded.
This way, for instance an ion exchanger for instance is monitored for
hardness breaking through.
If the programme switch S9 is in the OFF position, the exceedance
of a limit value is monitored.
If the programme switch S9 is in position ON, it is monitored
whether a limit value is undershot. This option may be applied in
case a blending unit has to be monitored where a minimum
hardness is required.
However, all functions with regard to signals and reactions of the
system described in the present operation manual refer to the limit
value being undershot.
Limit value monitoring
S9 Function
OFF
Indication that limit
value has been
exceeded
ON
Signal if value is
undershot
ON