Automatic water analysis system
GENO-softwatch Komfort
Order no. 145 172 955-inter Edited by: phar-mrie G:\BA-172955-INTER_145_GENO-SOFTWATCH KOMFORT
38
4.2.6 Input function
Input function
S10 Function
OFF No
analysis
ON
External analysis start
Flow controller function
Program switch S10 is set to OFF (delivery state).
This function is used if an analysis shall only be carried out when
water is withdrawn. This is particularly useful for discontinuous
processes.
The function is also used when no analyses are required, e.g. during
the regeneration of a single water softener.
Note:
In the as-delivered state, input IN (terminal 18/19) is bridged
and thus the flow controller function is active.
The external contact for the IN input (terminal 18/19) must always be
a potential-free switch.
The set time interval (S1 and S2) continues to expire when the
contact at the input is opened briefly.
Start
function
Program switch S10 is set to ON.
As soon as the voltage-free contact at input IN is closed, an analysis
is carried out every 5 minutes (independent of the switch positions S1
and S2). The first analysis starts immediately after the contact is
closed.
Note:
Instead of a flow controller, any other voltage-free contact of
a timer or a relay (osmose control unit, softener control unit) can be
used.