Automatic water analysis system
GENO-softwatch Komfort
Order no. 145 172 955-inter Edited by: phar-mrie G:\BA-172955-INTER_145_GENO-SOFTWATCH KOMFORT
23
2.4 Water connection
The connection must be established directly downstream of the water
treatment system. Keep the feed line to the GENO-softwatch Komfort
as short as possible and do not exceed a maximum length of
5 metres, if possible. It is essential that the line is directed straight up
to the water pipe in order to make sure that no dirt particles from the
water pipe are carried along to the system.
Hydraulic connection
1. Install T-piece provided by others on site (vertical installation
position below the inlet of the GENO-softwatch Komfort).
2. Mount the on-site adapter to reduce the thread to ¼" (female thread)
at the T-piece.
3. Screw a straight screw-in connector ¼" - 6 mm into the T-piece.
Note:
The max. screw-in torque for plastic fittings is 1.5 Nm.
4. Plug on the quick coupling with non-return valve at the nipple "IN"
of the device inlet.
5. Plug in the 6 mm feed hose, cut it to length and insert it in the
second threaded connector.
Waste
water
connection
6. Insert the 8 mm waste water hose at the system connection "OUT"
and cut to length.
Caution!
The drain connection must be made according to EN 1717.