22

MAINTENANCE CHART

Disconnect all power (AC, battery) to the operator before servicing. The operator's AC Power switch ONLY turns off AC power to the 
control board and DOES NOT turn off battery power. ALWAYS disconnect the batteries via the J15 plug to service the operator (refer 
page 10).

BATTERY MAINTENANCE

Batteries will degrade over time depending on temperature and usage. The operator alarm will beep 3 times with a command if the battery 
is low. Batteries do not perform well in extremely cold temperatures. For best performance, the batteries should be replaced every 3 years. 
Use only Grifco replacement batteries. The operator comes with two 7AH batteries. The batteries contain lead and need to be disposed of 
properly. If batteries are leaking, safely remove them and dispose of them properly. See page 9 for instructions.

DESCRIPTION

TASK

CHECK AT LEAST ONCE EVERY

MONTH

6 MONTHS

3 YEARS

Entrapment Protection 
Devices

Check and test for proper operation

X

Manual Disconnect

Check and test for proper operation

X

Door

Make sure the door operates smoothly without the operator

X

Door Track

Make sure the door track runs smoothly

X

Accessories

Check all for proper operation

X

Operator Rail

Inspect and maintain the rail to ensure there is no corrosion

X

Electrical

Inspect all wire connections and circuit boards for visible 
wear or damage

X

Operator

Inspect for wear or damage

X

Chain

Check tension and lubricate if needed

X

Batteries

Inspect the batteries and test the operator works without 
mains connected

Test

Replace

In coastal applications, extra care is required to prevent corrosion on rail and other metal components.

WARNING

WARNING

Always wear protective gloves and eye protection when changing the battery or working around the battery compartment. 

To reduce the risk of SEVERE INJURY or DEATH: READ AND 
FOLLOW ALL INSTRUCTIONS. 

•  ALL maintenance MUST be performed by a Grifco professional.

•  ANY maintenance to the operator or in the area near the  
  operator MUST NOT be performed until disconnecting the  
  electrical power 
 
  (AC or solar and battery) and locking-out the power via the  
  operator power switch. Upon completion of maintenance the  
  area MUST be cleared and secured, at that time the operator may  
  be returned to service.

•  NEVER let children operate or play with door controls. Keep the  
  transmitter away from children.

•  ALWAYS keep people and objects away from the door. NO ONE  
  SHOULD CROSS THE PATH OF THE MOVING DOOR.

•  The entrance is for vehicles ONLY. Pedestrians MUST use  
  separate entrance.

•  Test the door operator monthly. The door MUST reverse on  
  contact with a rigid object or reverse when an object activates  
  the non-contact sensors. After adjusting the force or the limit of  
  travel, retest the door operator. Failure to adjust and retest the  
  door operator properly can increase the risk of INJURY or  
 DEATH.

•  Use the manual disconnect release ONLY when the gate/door is  
  not moving.

•  KEEP DOOR PROPERLY MAINTAINED. Read the owner’s  
  manual. Have a qualified service person make repairs to door  
 hardware.

•  Activate gate/door ONLY when it can be seen clearly, is properly  
  adjusted and there are no obstructions to gate/door travel.

•  To reduce the risk of FIRE or INJURY to persons use ONLY  
  Grifco replacement batteries.

•  Dispose of used batteries properly

•  SAVE THESE INSTRUCTIONS.

MAINTENANCE

Содержание GSD-R2.4M

Страница 1: ...CIAN ONLY This operator is compatible with Security 2 0 accessories OPERATOR REQUIRES GRIFCO MONITORED ENTRAPMENT PROTECTION OPERATOR REQUIRES GRIFCO MONITORED ENTRAPMENT PROTECTION Commercial Section...

Страница 2: ...on responsible for their safety Children should be supervised to ensure that they do not play with the appliance If the operator is installed at a height less than 2 5 metres from floor level or any o...

Страница 3: ...ING 10 TYPES OF MONITORED ENTRAPMENT PROTECTION 11 SELECTION OF ENTRAPMENT PROTECTION SYSTEM 11 COMMISSIONING ENTRAPMENT PROTECTION SYSTEMS 12 FORCE SETTING AND FINE ADJUSTMENT 13 TYPES OF SECURITY 2...

Страница 4: ...s Rail Part No 2 4m GSD R2 4M 3 6m GSD R3 6M 6 0m GSD RKIT rail angle not supplied Maximum Door Weight 315 5 kg balanced door Maximum Door Area 26m Travel Speed 20cm per second Maximum Duty Cycle Cont...

Страница 5: ...NECTION RESET BUTTON ACCESS CONTROL DEVICE EXTERNAL TERMINAL BLOCK AC POWER SWITCH EMI BOARD INTRODUCTION PE Beams Sold Separately Make sure the door opens and closes smoothly Door should stay in the...

Страница 6: ...mitters and the network 7 TIMER TO CLOSE dial The TIMER TO CLOSE TTC dial can be set to automatically close the door after a specified time period The TTC is factory set to OFF If the TTC is set to th...

Страница 7: ...le is clear the door will continue to close 5 AUX RELAY Switches Set the AUX RELAY switches as need ed to obtain the desired function as shown on pages 20 21 6 EYE EDGE Switches Set the EYE EDGE switc...

Страница 8: ...7 Attach the push arm to the trolley test emergency release rope is operational Attach the J bar to the push arm 8 Attached J bar to door bracket after following STEP 3 on the next page Header Bracke...

Страница 9: ...egative terminal of the other battery 5 Insert the batteries as shown 6 Reattach the battery cover 7 Insert the J15 plug back into the control board This will power up the control board NOTE You may s...

Страница 10: ...n you program the limits but can be fine tuned using the REVERSAL FORCE dial on the control board refer to Fine Tune the Force section to compensate for environmental changes The limit setup LEDs loca...

Страница 11: ...iant safety sensors relying on a non monitored normally closed contact can be bypassed or fail to operate in the event of damage or tampering Entrapment Protection Systems must be monitored to form pa...

Страница 12: ...tion PE beams with selectable functionality EYE EDGE and COM x2 Open or Close direction PE Beams OR contact edge sensors with selectable functionality DIP SWITCH SETTINGS The DIP Switches located next...

Страница 13: ...stop the door After any adjustments are made test the operator 1 Open and close the door with the TEST BUTTONS ensuring that the door is stopping at the proper open and close limit positions 2 Place a...

Страница 14: ...r for vehicle or forklift mounting Security 2 0 Part No E945G Description 3 channel keyring transmitter Security 2 0 Part No E960G Description 4 channel keyring transmitter Security 2 0 Security Part...

Страница 15: ...as an open close and stop 1 Press and release the LEARN button operator will beep and green XMITTER LED will light NOTE The operator will time out of programming mode after 30 seconds 2 Press the remo...

Страница 16: ...his automatically sets the force When limits are set properly the operator will automatically exit limit setting mode ADJUST THE LIMITS if needed If the limits have already been set the operator will...

Страница 17: ...lose at OPEN limit INTERRUPT 2 Terminals This input is used for photoelectric sensors and external interrupt loop detector when loop is on the outside of the door Holds open door at open limit Stops a...

Страница 18: ...f sight Bypasses any prewarning delay ACCESSORY POWER 24 VDC MAX 500 MA 4 Terminals SWITCHED Switched ON when the door is in motion Turns off after a 5 second delay when the door stops The power will...

Страница 19: ...ure or out of balance conditions OPERATOR ALARM The operator alarm will beep 3 times with a command if the battery is low When the inherent force of the operator RPM current sensor detects the followi...

Страница 20: ...sual display connect an external buzzer or light low voltage Energizes if gate door is manually tampered with by being pushed off of close limit For an additional audible or visual display connect an...

Страница 21: ...es not reset alarm condition E Stop Input common 3 PB station 4 terminals total Stop command stops a moving door Hard stop maintained switch overrides Open and Close commands and resets alarm conditio...

Страница 22: ...ications extra care is required to prevent corrosion on rail and other metal components WARNING WARNING Always wear protective gloves and eye protection when changing the battery or working around the...

Страница 23: ...ect against fire and electrocution DISCONNECT power AC or solar and battery BEFORE installing or servicing operator For continued protection against fire Replace ONLY with fuse of same type and rating...

Страница 24: ...tivity TO RESET THE CODE HISTORY 1 Press and hold the STOP button for six seconds The display will show Er then CL alternately for six seconds 2 Release the STOP button The code history has now been r...

Страница 25: ...be set too tightly against a non resilient hard stop re adjust limit Operator may be at end of travel re adjust mounting NO 40 Battery overvoltage Too much voltage on the battery Check harness Make s...

Страница 26: ...canceling TTC 72 OPEN EYE EDGE triggered causing reversal or preventing opening 73 CLOSE EYE INTERRUPT triggered causing reversal preventing close or resetting TTC IF an obstruction occurred no actio...

Страница 27: ...charger or Solar power available BATT CHARGING OFF Not charging ON Three stage battery charging TIMER OFF The timer is disabled ON The timer is enabled MEDIUM BLINK 1 blink per second The timer is run...

Страница 28: ...active a Check all Open and Close inputs for a stuck on input b Check Stop button is not stuck on c Check Reset button d Charges batteries or replace batteries e Check all Entrapment Protection Device...

Страница 29: ...ion b Replace defective photoelectric sensor Retest that obstructing photoelectric sensor causes moving door to stop and may reverse direction Edge Sensor does not stop or reverse door a Incorrect edg...

Страница 30: ...setting incorrect b Interrupt loop detector c Defective Expansion board a Check that Anti Tail setting is ON b Check operation of Interrupt Loop detector c Replace defective Expansion board AUX Relay...

Страница 31: ...e Recti er EXPANSION BOARD Black Purple Brown Blue Gray Orange Orange Red Black Red CONTROL BOARD Piezo Alarm APS Encoder 1 2 HP 24 Vdc Motor ID Resistor White White Black Red Black Blue Red Reset But...

Страница 32: ...ights and remedies as a consumer charge you a fee to repair replace and or return the Operator to you This Chamberlain Limited Warranty does not cover any failure of or defect in the Operator due to 1...

Отзывы: