CYCLE COUNT 

To determine the actual cycles that the door operator has run (in thousands), set all three Aux Relay switches to the ON setting for Aux 
Relay 1. The Expansion Board’s 1, 2, and 3 LEDs will blink out the cycle count.

•  1 LED blinking 1000’s 
•  2 LED blinking 10,000’s 
•  3 LED blinking 100,000’s 
•  Simultaneously all three LED’s blink 1,000,000’s

Cycle count displayed is between 1,000 and 9,999,000 cycles. After servicing, set Aux Relay switches back to their appropriate positions. 
Cycle count cannot be reset or changed. If under 1,000 cycles the 1, 2, and 3 LEDs will turn on for 10 seconds, then turn off.   
NOTE: The expansion board will flash the cycle count 3 times then all the LEDs will turn on solid for 10 seconds then turn off. 

AUXILIARY RELAYS

AUX RELAY 

SETTING

SWITCH 

SETTINGS

AUX RELAY 1

AUX RELAY 2

1

2

3

Off (no feature 

selected)

OFF

OFF

OFF

Relay always off. Use this Aux Relay setting to conserve battery power. 

Open Limit 

Switch

OFF

OFF

ON

Energizes at open limit.

Close Limit 

Switch

OFF

ON

OFF

Energizes when not at close limit. For an additional audible or visual display, 

connect an external light (low voltage).

Door Motion

OFF

ON

ON

Energizes when motor is on (door in motion). For an additional audible or visual display, 

connect an external buzzer or light (low voltage). 

Pre-Motion Delay

ON

OFF

OFF

Energizes 3 seconds before door motion and remains 
energized during door motion. The on board alarm will 
sound. For an additional audible or  Visual display, connect 
an external buzzer or light (low voltage). 

Energizes 3 seconds before door motion and 
remains energized during door motion.   
For an additional audible or visual display, 
connect an external buzzer or light (low voltage). 

Power

ON

ON

OFF

Energizes when AC power or solar power is present. There 
is approximately a 10-12 second delay before relay cutoff, 
after AC shutdown. 

Energizes when on battery power. There is 
approximately a 10-12 second delay before relay 
cutoff, after AC shutdown. 

Tamper

ON

OFF

ON

Energizes if gate/door is manually tampered with by being 
pushed off of close limit. For an additional audible or visual 
display, connect an external buzzer or light (low voltage). 

Energizes if gate/door is manually tampered with by 
being pushed off of close limit.   
For an additional audible or visual display, connect 
an external buzzer or light (low voltage). 

Cycle Quantity 

Feedback*

ON

ON

ON

The 1, 2, and 3 LEDs will blink out the cycle count (cycle 
count is stored on the control board).  See below. 

Red/green light functionality. See BELOW. 

AUX RELAY 1 AND 2

Normally Open (N.O.) and Normally Closed (N.C.) relay contacts to control external devices, for connection low voltage (42 Vdc [34 Vac] max 
5 Amps) power sources only.  

EXPANSION BOARD

SHADOW   INTERUPT      EXIT

SBC

OPN

CLS

STP

COM

EYE

ONLY

EYE/

EDGE

EYE/

EDGE

COM

1

2

3

OPE

N

CLOS

E

T

O MAIN

BOARD

POWER

 SHADOW   INTERRUPT      EXIT

AUX RELAY 1

AUX RELAY 2

A

UX Relay 2 N.C.

Com

AUX Relay 2 N.O.

AUX Relay 1 N.C.

Com

AUX Relay 1 N.O.

AUX RELAY WIRING EXAMPLE

Aux Relay

Class 2 Power Source  
(42 Vdc [34 Vac], 
5 A max)

Warning 
Light

COM

N.C.

N.O.

+

_

AUXILIARY RELAY WIRING 
EXAMPLE

AUX RELAY 1 AND 2 WIRING DETAILS 

Switch Settings

1

2

3

RELAY 1

RELAY 2

OFF

OFF

OFF

Relay always off

Relay always on

OFF

OFF

ON

Energises at open limit

Energises at open limit

OFF

ON

OFF

Energises when not at 

close limit

Energises when not at 

close limit

OFF

ON

ON

Energises when motor 

is on

Enegerises when motor 

is on

ON

OFF

OFF

Energises and alarms 3 

secods prior and during 

door automation

Energises 3 secods 

prior and during door 

automation

ON

ON

ON

Energises when door is 

tampered with

Energises when door is 

tampered with

ON

OFF

ON

LEDs will blink cycle 

count

Red / Green light 

functionality

ON

ON

ON

Red

 / 

Green

 Light Functionality

Red

 light wired to AUX RELAY 1 

Green

 Light wired to AUX RELAY 2

Door State

AUX RELAY 1 SWITCHES

AUX RELAY 2 SWITCHES

1 OFF

2 OFF

3 OFF

1 ON

2 ON

3 ON

CLOSED

Red light OFF*

Green light OFF

OPENING

Red light ON / FLASH

Green light OFF

OPEN

Red light OFF

Green light ON

CLOSING

red light ON / FLASH

Green light OFF

Defined mid stop

N/A

N/A

Undefined mid 

stop

Red light ON

Green light OFF

Timer more than 

5 seconds

Red light OFF

Green light ON

Timer less than 

5 seconds

Red light ON / FLASH

Green light OFF

* For 

red light ON

 when door is closed, set switch on AUX RELAY 1 to ON

For example, 1 LED blinks 3 
times, 2 LED blinks 6 times, 
and 3 LED blinks once. 
Cycle count is 163,000.

Содержание GSD-R2.4M

Страница 1: ...CIAN ONLY This operator is compatible with Security 2 0 accessories OPERATOR REQUIRES GRIFCO MONITORED ENTRAPMENT PROTECTION OPERATOR REQUIRES GRIFCO MONITORED ENTRAPMENT PROTECTION Commercial Section...

Страница 2: ...on responsible for their safety Children should be supervised to ensure that they do not play with the appliance If the operator is installed at a height less than 2 5 metres from floor level or any o...

Страница 3: ...ING 10 TYPES OF MONITORED ENTRAPMENT PROTECTION 11 SELECTION OF ENTRAPMENT PROTECTION SYSTEM 11 COMMISSIONING ENTRAPMENT PROTECTION SYSTEMS 12 FORCE SETTING AND FINE ADJUSTMENT 13 TYPES OF SECURITY 2...

Страница 4: ...s Rail Part No 2 4m GSD R2 4M 3 6m GSD R3 6M 6 0m GSD RKIT rail angle not supplied Maximum Door Weight 315 5 kg balanced door Maximum Door Area 26m Travel Speed 20cm per second Maximum Duty Cycle Cont...

Страница 5: ...NECTION RESET BUTTON ACCESS CONTROL DEVICE EXTERNAL TERMINAL BLOCK AC POWER SWITCH EMI BOARD INTRODUCTION PE Beams Sold Separately Make sure the door opens and closes smoothly Door should stay in the...

Страница 6: ...mitters and the network 7 TIMER TO CLOSE dial The TIMER TO CLOSE TTC dial can be set to automatically close the door after a specified time period The TTC is factory set to OFF If the TTC is set to th...

Страница 7: ...le is clear the door will continue to close 5 AUX RELAY Switches Set the AUX RELAY switches as need ed to obtain the desired function as shown on pages 20 21 6 EYE EDGE Switches Set the EYE EDGE switc...

Страница 8: ...7 Attach the push arm to the trolley test emergency release rope is operational Attach the J bar to the push arm 8 Attached J bar to door bracket after following STEP 3 on the next page Header Bracke...

Страница 9: ...egative terminal of the other battery 5 Insert the batteries as shown 6 Reattach the battery cover 7 Insert the J15 plug back into the control board This will power up the control board NOTE You may s...

Страница 10: ...n you program the limits but can be fine tuned using the REVERSAL FORCE dial on the control board refer to Fine Tune the Force section to compensate for environmental changes The limit setup LEDs loca...

Страница 11: ...iant safety sensors relying on a non monitored normally closed contact can be bypassed or fail to operate in the event of damage or tampering Entrapment Protection Systems must be monitored to form pa...

Страница 12: ...tion PE beams with selectable functionality EYE EDGE and COM x2 Open or Close direction PE Beams OR contact edge sensors with selectable functionality DIP SWITCH SETTINGS The DIP Switches located next...

Страница 13: ...stop the door After any adjustments are made test the operator 1 Open and close the door with the TEST BUTTONS ensuring that the door is stopping at the proper open and close limit positions 2 Place a...

Страница 14: ...r for vehicle or forklift mounting Security 2 0 Part No E945G Description 3 channel keyring transmitter Security 2 0 Part No E960G Description 4 channel keyring transmitter Security 2 0 Security Part...

Страница 15: ...as an open close and stop 1 Press and release the LEARN button operator will beep and green XMITTER LED will light NOTE The operator will time out of programming mode after 30 seconds 2 Press the remo...

Страница 16: ...his automatically sets the force When limits are set properly the operator will automatically exit limit setting mode ADJUST THE LIMITS if needed If the limits have already been set the operator will...

Страница 17: ...lose at OPEN limit INTERRUPT 2 Terminals This input is used for photoelectric sensors and external interrupt loop detector when loop is on the outside of the door Holds open door at open limit Stops a...

Страница 18: ...f sight Bypasses any prewarning delay ACCESSORY POWER 24 VDC MAX 500 MA 4 Terminals SWITCHED Switched ON when the door is in motion Turns off after a 5 second delay when the door stops The power will...

Страница 19: ...ure or out of balance conditions OPERATOR ALARM The operator alarm will beep 3 times with a command if the battery is low When the inherent force of the operator RPM current sensor detects the followi...

Страница 20: ...sual display connect an external buzzer or light low voltage Energizes if gate door is manually tampered with by being pushed off of close limit For an additional audible or visual display connect an...

Страница 21: ...es not reset alarm condition E Stop Input common 3 PB station 4 terminals total Stop command stops a moving door Hard stop maintained switch overrides Open and Close commands and resets alarm conditio...

Страница 22: ...ications extra care is required to prevent corrosion on rail and other metal components WARNING WARNING Always wear protective gloves and eye protection when changing the battery or working around the...

Страница 23: ...ect against fire and electrocution DISCONNECT power AC or solar and battery BEFORE installing or servicing operator For continued protection against fire Replace ONLY with fuse of same type and rating...

Страница 24: ...tivity TO RESET THE CODE HISTORY 1 Press and hold the STOP button for six seconds The display will show Er then CL alternately for six seconds 2 Release the STOP button The code history has now been r...

Страница 25: ...be set too tightly against a non resilient hard stop re adjust limit Operator may be at end of travel re adjust mounting NO 40 Battery overvoltage Too much voltage on the battery Check harness Make s...

Страница 26: ...canceling TTC 72 OPEN EYE EDGE triggered causing reversal or preventing opening 73 CLOSE EYE INTERRUPT triggered causing reversal preventing close or resetting TTC IF an obstruction occurred no actio...

Страница 27: ...charger or Solar power available BATT CHARGING OFF Not charging ON Three stage battery charging TIMER OFF The timer is disabled ON The timer is enabled MEDIUM BLINK 1 blink per second The timer is run...

Страница 28: ...active a Check all Open and Close inputs for a stuck on input b Check Stop button is not stuck on c Check Reset button d Charges batteries or replace batteries e Check all Entrapment Protection Device...

Страница 29: ...ion b Replace defective photoelectric sensor Retest that obstructing photoelectric sensor causes moving door to stop and may reverse direction Edge Sensor does not stop or reverse door a Incorrect edg...

Страница 30: ...setting incorrect b Interrupt loop detector c Defective Expansion board a Check that Anti Tail setting is ON b Check operation of Interrupt Loop detector c Replace defective Expansion board AUX Relay...

Страница 31: ...e Recti er EXPANSION BOARD Black Purple Brown Blue Gray Orange Orange Red Black Red CONTROL BOARD Piezo Alarm APS Encoder 1 2 HP 24 Vdc Motor ID Resistor White White Black Red Black Blue Red Reset But...

Страница 32: ...ights and remedies as a consumer charge you a fee to repair replace and or return the Operator to you This Chamberlain Limited Warranty does not cover any failure of or defect in the Operator due to 1...

Отзывы: