20
CYCLE COUNT
To determine the actual cycles that the door operator has run (in thousands), set all three Aux Relay switches to the ON setting for Aux
Relay 1. The Expansion Board’s 1, 2, and 3 LEDs will blink out the cycle count.
• 1 LED blinking 1000’s
• 2 LED blinking 10,000’s
• 3 LED blinking 100,000’s
• Simultaneously all three LED’s blink 1,000,000’s
Cycle count displayed is between 1,000 and 9,999,000 cycles. After servicing, set Aux Relay switches back to their appropriate positions.
Cycle count cannot be reset or changed. If under 1,000 cycles the 1, 2, and 3 LEDs will turn on for 10 seconds, then turn off.
NOTE: The expansion board will flash the cycle count 3 times then all the LEDs will turn on solid for 10 seconds then turn off.
AUXILIARY RELAYS
AUX RELAY
SETTING
SWITCH
SETTINGS
AUX RELAY 1
AUX RELAY 2
1
2
3
Off (no feature
selected)
OFF
OFF
OFF
Relay always off. Use this Aux Relay setting to conserve battery power.
Open Limit
Switch
OFF
OFF
ON
Energizes at open limit.
Close Limit
Switch
OFF
ON
OFF
Energizes when not at close limit. For an additional audible or visual display,
connect an external light (low voltage).
Door Motion
OFF
ON
ON
Energizes when motor is on (door in motion). For an additional audible or visual display,
connect an external buzzer or light (low voltage).
Pre-Motion Delay
ON
OFF
OFF
Energizes 3 seconds before door motion and remains
energized during door motion. The on board alarm will
sound. For an additional audible or Visual display, connect
an external buzzer or light (low voltage).
Energizes 3 seconds before door motion and
remains energized during door motion.
For an additional audible or visual display,
connect an external buzzer or light (low voltage).
Power
ON
ON
OFF
Energizes when AC power or solar power is present. There
is approximately a 10-12 second delay before relay cutoff,
after AC shutdown.
Energizes when on battery power. There is
approximately a 10-12 second delay before relay
cutoff, after AC shutdown.
Tamper
ON
OFF
ON
Energizes if gate/door is manually tampered with by being
pushed off of close limit. For an additional audible or visual
display, connect an external buzzer or light (low voltage).
Energizes if gate/door is manually tampered with by
being pushed off of close limit.
For an additional audible or visual display, connect
an external buzzer or light (low voltage).
Cycle Quantity
Feedback*
ON
ON
ON
The 1, 2, and 3 LEDs will blink out the cycle count (cycle
count is stored on the control board). See below.
Red/green light functionality. See BELOW.
AUX RELAY 1 AND 2
Normally Open (N.O.) and Normally Closed (N.C.) relay contacts to control external devices, for connection low voltage (42 Vdc [34 Vac] max
5 Amps) power sources only.
EXPANSION BOARD
SHADOW INTERUPT EXIT
SBC
OPN
CLS
STP
COM
EYE
ONLY
EYE/
EDGE
EYE/
EDGE
COM
1
2
3
OPE
N
CLOS
E
T
O MAIN
BOARD
POWER
SHADOW INTERRUPT EXIT
AUX RELAY 1
AUX RELAY 2
A
UX Relay 2 N.C.
Com
AUX Relay 2 N.O.
AUX Relay 1 N.C.
Com
AUX Relay 1 N.O.
AUX RELAY WIRING EXAMPLE
Aux Relay
Class 2 Power Source
(42 Vdc [34 Vac],
5 A max)
Warning
Light
COM
N.C.
N.O.
+
_
AUXILIARY RELAY WIRING
EXAMPLE
AUX RELAY 1 AND 2 WIRING DETAILS
Switch Settings
1
2
3
RELAY 1
RELAY 2
OFF
OFF
OFF
Relay always off
Relay always on
OFF
OFF
ON
Energises at open limit
Energises at open limit
OFF
ON
OFF
Energises when not at
close limit
Energises when not at
close limit
OFF
ON
ON
Energises when motor
is on
Enegerises when motor
is on
ON
OFF
OFF
Energises and alarms 3
secods prior and during
door automation
Energises 3 secods
prior and during door
automation
ON
ON
ON
Energises when door is
tampered with
Energises when door is
tampered with
ON
OFF
ON
LEDs will blink cycle
count
Red / Green light
functionality
ON
ON
ON
Red
/
Green
Light Functionality
Red
light wired to AUX RELAY 1
Green
Light wired to AUX RELAY 2
Door State
AUX RELAY 1 SWITCHES
AUX RELAY 2 SWITCHES
1 OFF
2 OFF
3 OFF
1 ON
2 ON
3 ON
CLOSED
Red light OFF*
Green light OFF
OPENING
Red light ON / FLASH
Green light OFF
OPEN
Red light OFF
Green light ON
CLOSING
red light ON / FLASH
Green light OFF
Defined mid stop
N/A
N/A
Undefined mid
stop
Red light ON
Green light OFF
Timer more than
5 seconds
Red light OFF
Green light ON
Timer less than
5 seconds
Red light ON / FLASH
Green light OFF
* For
red light ON
when door is closed, set switch on AUX RELAY 1 to ON
For example, 1 LED blinks 3
times, 2 LED blinks 6 times,
and 3 LED blinks once.
Cycle count is 163,000.