Installation of Outdoor Unit
● Cautions on Installation of Outdoor Unit
To ensure good operation of the air conditioner, the selection of installing position must be in accordance
with the following principles:
The outdoor unit shall be so installed that the air discharged out of the outdoor unit will not flow back and
that enough space shall be maintained around the machine for repair.
The installing position shall be in good ventilation, so that the machine can breathe and exhaust enough
air. Ensure that there is no obstruction at the inlet and outlet of the machine. If any, please remove the
obstructions blocking the air inlet and outlet.
The installing position shall be strong enough to withstand the weight of outdoor unit and be able to
isolate the sound and absorb the vibration. Also ensure that the outlet air and noise from the air conditioner
will not affect the neighbors.
The outdoor unit must be lifted by using the designated lift hole. During lifting, take care to protect the air
conditioner and avoid knocking the metal parts, thus to prevent rusting in the future.
Avoid direct sunshine as it might be.
The installing position must be able to drain the rainwater and the water generated from defrosting.
The installing position must ensure that the machine will not be buried in the snow or affected by the
wastes or oil mist.
To meet the noise and vibration requirements, the outdoor unit shall be installed by using rubber
damping pad or spring damper.
The installing dimension shall comply with the installation requirements in these instructions. The outdoor
unit must be fixed at the installing position.
☆
The installation shall be done by specialist technicians.
● Installation of Outdoor Unit
1. Overall Dimension of Outdoor Unit
Overall Dimensional Schematics for GMV-Pds100W/Na-K, GMV-Pds120W/Na-K,
GMV-Pds140W/Na-K and GMV-Pds160W/Na-K
Fig. 1
2. When moving the outdoor unit, two ropes with enough length must be used to lift in four directions. To
prevent the machine from drifting out of the center, the included angle of the ropes must be smaller than
40
0
when the machine is being lifted and moved.
3. Fasten the machine onto the supporting legs and base with M12 screw combination.
4. The outdoor unit shall be installed on concrete foundation 10cm high.
5. For the space dimensions required for installation of the machine body, please see below.