26
Refrigerant Charging and Test Run
Liquid Pipe:
No.
A
B
C
D
E
Diameter
φ9.52
φ9.52
φ9.52
φ6.35
Φ12.7
Length
20m
10m
5m
5m
5m
No.
a
b
c
d
Diameter
φ9.52
φ6.35
φ6.35
φ6.35
Length
10m
10m
10m
10m
Total length of liquid pipes
Φ12.7 E=5=5m
φ9.52 A+B+C+a=20+10+5+10=45m
φ6.35:D+b+c+d=5+10+10+10=35m
Note: It is not needed to add refrigerant if the total length of liquid pipe is within 50m.
Therefore, the total length of 9.52 liquid pipe L (total length of 12.7 liquid pipe *2)+(total length of 9.52
liquid pipe *1)+(total length of 6.35 liquid pipe *0.4) (5m*2)+(45m*1)+(35m*0.4) 69m and the minimum
refrigerant volume to be added (69-50) X0.054 1.026kg.
Amount of Additional Refrigerant for Hydro
-box
:8kw*0.054 kg/Kw=0.432kg
Total amount of additional
Refrigerant for the whole system: 1.026kg.+ 0.432kg=1.458kg
Содержание GMV-Pds100W/Na-K