35
Troubleshooting
Error
Display on
numerical tube
of outdoor unit
Display of Error Lamp
Display on Indoor
Manipulator
LED6
LED5
LED4
LED3
LED2
LED1
DC busbar overvoltage
protection
PH
Bright
Flash
Bright
Bright
Bright
Bright
E5
Radiating fin overheat
protection
P8
Bright
Flash
Bright
Bright
Bright
Flash
E5
Current sensor fault
Pc
Bright
Flash
Bright
Bright
Flash
Bright
E5
Radiator sensor fault
P7
Bright
Flash
Bright
Flash
Bright
Bright
E5
Compressor current
protection
P5
Bright
Flash
Bright
Flash
Bright
Flash
E5
Low-voltage protection
PL
Bright
Flash
Bright
Flash
Flash
Bright
E5
Failed to start
Lc
Bright
Flash
Dark
Bright
Bright
Bright
E5
PFC abnormal
Hc
Bright
Flash
Dark
Bright
Bright
Dark
E5
Compressor clogged
LE
Bright
Flash
Dark
Bright
Bright
Flash
E5
IPM module reset
P0
Bright
Flash
Dark
Bright
Dark
Bright
E5
Motor out of synchronization
H7
Bright
Flash
Dark
Bright
Dark
Dark
E5
Open phase, tripping
Ld
Bright
Flash
Dark
Bright
Dark
Flash
E5
Fault from variable frequency
drive to main control
communication
P6
Bright
Bright
Dark
Dark
Dark
Flash
E5
IPM module protection
H5
Bright
Flash
Flash
Bright
Bright
Bright
E5
Overspeed
LF
Bright
Flash
Flash
Bright
Bright
Dark
E5
Sensor
connection
protection
Pd
Bright
Flash
Flash
Bright
Bright
Flash
E5
Temperature drift protection
PE
Bright
Flash
Flash
Bright
Dark
Bright
E5
AC contactor protection
P9
Bright
Flash
Flash
Bright
Dark
Dark
E5
High-pressure protection
E1
Bright
Flash
Dark
Dark
Dark
Flash
E1
Low-pressure protection
E3
Bright
Flash
Dark
Dark
Flash
Dark
E3
Exhaust protection
E4
Bright
Flash
Dark
Dark
Flash
Flash
E4
Compressor overload
protection
H3
Bright
Flash
Dark
Flash
Dark
Dark
E5
Communication fault
(between indoor / outdoor
unit and hand controller)
E6
Bright
Flash
Dark
Flash
Flash
Dark
E6
Outdoor environment
temperature sensor error
F4
Bright
Flash
Flash
Dark
Dark
Dark
F4
Indoor coil inlet temperature
sensor error
F5
Bright
Flash
Flash
Dark
Dark
Flash
F5
Indoor coil middle
temperature sensor error
F6
Bright
Flash
Flash
Dark
Flash
Dark
F6
Indoor coil outlet temperature
sensor error
F7
Bright
Flash
Flash
Dark
Flash
Flash
F7
Variable-frequency exhaust
temperature sensor error
F9
Bright
Flash
Flash
Flash
Dark
Flash
F9
AC current protection (input
side)
PA
Bright
Flash
Bright
Flash
Bright
Dark
E5
Driver board environment
temperature sensor error
PF
Bright
Flash
Bright
Flash
Dark
Bright
E5
AC input voltage abnormal
PP
E5
Jumper fault
C5
No display
Recharging circuit fault
PU
E5
●
After-sale Services
☆
If your air conditioner has quality or other problems, please contact Gree’s after-sale Service
Department. For details, please see the Service Telephones of Gree Electric Appliance Inc. in Each
Province (City).
Содержание GMV-Pds100W/Na-K