6
Selection of Installing Position and Precautions
● Cable Layout
Carry out installation according to local cabling rules.
Rated supply voltage and special circuit for air conditioner must be used.
Do not pull the power cables with force.
All the electric installations must be carried out by specialist technicians in accordance with the local
laws, rules and these instructions.
The diameter of power cords must be large enough. The damaged power cords and connection wires
must be replaced with special cords.
☆
The earthing shall be secure. The earthing wire shall be connected to the special earthing device on
the construction. The installation must be done by specialist technicians. The fixed circuit must be
provided with leakage protections witch and air switch that have enough capacity. The air switch shall
have both the magnetic tripping and thermal tripping functions to ensure protection against the short
circuit and overload.
Model
Power Supply
Air Switch Capacity
Recommended Wire
(Number x Section)
GMV-Pds100W/Na-K
220V~ 50Hz
32
3×6.0
GMV-Pds120W/Na-K
220V~ 50Hz
32
3×6.0
GMV-Pds140W/Na-K
220V~ 50Hz
40
3×10.0
GMV-Pds160W/Na-K
220V~ 50Hz
40
3×10.0
● Earthing Requirements
The air conditioner belongs to Category I Electric Appliance. Therefore, be sure to take reliable earthing
measures.
The yellow-green wire inside the air conditioner is used for earthing. Do not use it for other purposes or
cut it. Do not fix with tapping screw. Otherwise, it will cause the risk of electric shock.
The earthing resistance shall comply with the Chinese standard GB17790.
Reliable earthing terminal must be provided on the user’s power supply. Never connect the earthing wire
to the following places:
Water pipe; Gas pipe; Sewage pipe;
Other places that the specialist technicians think unreliable.
● Noise
Install the air conditioner at a well-ventilating place. If not, the working capacity will be reduced or the
noise will be increased.
The air conditioner shall be firmly installed on a base that can adequately support its weight. Otherwise,
vibration and noise will be caused.
The outdoor unit shall be so installed that the hot air or noise will not affect the neighbors or environment
around.
There shall be no obstructions piled at the air outlet of the outdoor unit. Otherwise, the working capacity
will be reduced or the noise will be increased.
In the event that any abnormal sound occurs during use, please immediately contact the vendor.
● Accessories for Installation
For the accessories for installation of the indoor units and outdoor unit, please refer to the packing list
included in respective package.