GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
92
Step 8: If the n7 parameter query is selected, the display is as follows. Enter the to-be-confirmed
status of parameter query.
LED1
LED2
LED3
Function Code
Display Mode
Current Progress/Mode
Display Mode
Current Status Display Mode
n7
Blinking
00
Blinking
00
Blinking
On the master unit, press "SW7" to confirm parameter query and enter the module confirmation
status for parameter query. The display is as follows:
LED1
LED2
LED3
Function Code
Display Mode
Module Address
Display Mode
Current Status
Display Mode
n7
On
01
Blinking
00
Blinking
n7
On
02
Blinking
00
Blinking
n7
On
03
Blinking
00
Blinking
n7
On
04
Blinking
00
Blinking
Select a module for parameter query by pressing "SW1 (UP)" or "SW2 (DOWN)" and then press
"SW7". The display is as follows:
LED1
LED2
LED3
Function Code
Display Mode
Parameter Code
Display Mode
Current Status
Display Mode
n7
On
XX
On
Parameter value
Blinking
LED2 displays the parameter code of the module and LED3 displays the parameter value.
Parameters are displayed in the following sequence. By default, the outdoor environment temperature
value is displayed. Select a corresponding parameter value by pressing "SW1 (UP)" or "SW2 (DOWN)".
Parameter Code
Parameter Name
Unit
Remark
01
Outdoor environment temperature
°C
02
Operation frequency of compressor 1
Hz
03
Operation frequency of compressor 2
Hz
04
Operation frequency of outdoor fan
Hz
05
Module high-pressure
°C
06
Module low-pressure
°C
07
Discharge temperature of compressor 1
°C
08
Discharge temperature of compressor 2
°C
09
Discharge temperature of compressor 3
°C
This parameter is invalid for the GMV5E
series.
10
Discharge temperature of compressor 4
°C
This parameter is invalid for the GMV5E
series.
11
Discharge temperature of compressor 5
°C
This parameter is invalid for the GMV5E
series.
12
Discharge temperature of compressor 6
°C
This parameter is invalid for the GMV5E
series.
13
Operation frequency of compressor 3
Hz
This parameter is invalid for the GMV5E
series.
14
Current value of compressor 1
A
15
Current value of compressor 2
A
16
Current value of compressor 3
A
This parameter is invalid for the GMV5E
series.
17
Current value of compressor 4
A
This parameter is invalid for the GMV5E
series.
18
Current value of compressor 5
A
This parameter is invalid for the GMV5E
series.
19
Current value of compressor 6
A
This parameter is invalid for the GMV5E