GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
8
Model
GMV-680WM/E-
X
GMV-730WM/E-
X
GMV-785WM/E-
X
GMV-850WM/E-
X
GMV-900WM/E-
X
Refrigeration Capacity
HP
24
26
28
30
32
Combination Mode
—
GMV-280WM/E-
X +
GMV-400WM/E-
X
GMV-280WM/E-
X +
GMV-450WM/E-
X
GMV-280WM/E-
X +
GMV-504WM/E-
X
GMV-280WM/E-
X +
GMV-560WM/E-
X
GMV-280WM/E-
X +
GMV-615WM/E-
X
Power Supply
-
380-415V 3N~ 50Hz/60Hz
Rated
Capacity
Cooling
Nom.
kW
68
73
78.4
84
89.5
Heating
Nom
kW
76.5
81.5
81.9
87.5
93
Max
kW
76.5
81.5
88
94.5
100.5
Dimensions
(W × D × H)
mm
930×765
×1605+1340
×765×1605
930×765×1605
+1340×765
×1740
930×765×1605
+1340×765
× 1740
930×765×1605
+1340×765
× 1740
930×765
×1605+1340
×765×1740
Tubing
Dimensions
Liquid Pipe mm
Φ15.9
Φ19.05
Φ19.05
Φ19.05
Φ19.05
Gas Pipe
mm
Φ28.6
Φ31.8
Φ31.8
Φ31.8
Φ31.8
Balance pipe mm
Φ9.52
Φ9.52
Φ9.52
Φ9.52
Φ9.52
Weight
kg
235+360
235+360
235+360
235+385
235+385
Refrigerant
Name
-
R410A
R410A
R410A
R410A
R410A
Built-in Filling
Volume
kg
9.0+9.8
9.0+10.3
9.0+11.3
9.0+14.3
9.0+14.3
Model
GMV-960WM/
E-X
GMV-1010WM
/E-X
GMV-1065WM
/E-X
GMV-1130WM/
E-X
GMV-1180WM/
E-X
Refrigeration Capacity
HP
34
36
38
40
42
Combination Mode
—
GMV-335WM/
E-X +
GMV-615WM/
E-X
GMV-400WM/
E-X+
GMV-615WM/
E-X
GMV-450WM/
E-X+
GMV-615WM/
E-X
GMV-504WM/
E-X +
GMV-615WM/
E-X
GMV-560WM/
E-X +
GMV-615WM/
E-X
Power Supply
-
380-415V 3N~ 50Hz/60Hz
Rated
Capacity
Cooling
Nom.
kW
95
101.5
106.5
111.9
117.5
Heating
Nom
kW
99
106.5
111.5
111.9
117.5
Max
kW
106.5
114
119
125.5
132
Dimensions
(W × D × H)
mm
1340×765
×1605+1340
×765×1740
1340×765
×1605+1340
×765×1740
1340×765
×1740+1340
×765×1740
1340×765
×1740+1340
×765×1740
1340×765
×1740+1340
×765×1740
Tubing
Dimensions
Liquid
Pipe
mm
Φ19.05
Φ19.05
Φ19.05
Φ19.05
Φ19.05
Gas Pipe mm
Φ31.8
Φ38.1
Φ38.1
Φ38.1
Φ38.1
Balance
pipe
mm
Φ9.52
Φ9.52
Φ9.52
Φ9.52
Φ9.52
Weight
kg
285+385
360+385
360+385
360+385
385+385
Refrigerant
Name
-
R410A
R410A
R410A
R410A
R410A
Built-in
Filling
Volume
kg
8.2+14.3
9.8+14.3
10.3+14.3
11.3+14.3
14.3+14.3
Содержание /E-X
Страница 27: ...GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL 23 Any nonconformity must be resolved through coordination...
Страница 233: ...GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL 229 Troubleshooting...
Страница 239: ...GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL 235 Troubleshooting...
Страница 308: ...JF00303085...