GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
183
Troubleshooting:
2.2.4.64
“F8” Compressor 4 discharge temperature sensor error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
Sample the AD value of temperature sensors through temperature sensors circuit and judge the
range of AD value; if the sampled AD value exceeds upper limit and lower limit in 30 seconds
continuously, report the error.
Possible reason
:
■Poor contact between discharge temperature sensor and terminal in mainboard interface
■Discharge temperature sensor is abnormal
■Detecting circuit is abnormal
Содержание /E-X
Страница 27: ...GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL 23 Any nonconformity must be resolved through coordination...
Страница 233: ...GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL 229 Troubleshooting...
Страница 239: ...GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL 235 Troubleshooting...
Страница 308: ...JF00303085...