GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
13
area must be expanded to prevent overload current from burning the wire or causing fire hazard.
⑦
Specification of circuit breaker is based on the working condition where the ambient temperature
of circuit breaker is 40°C. If working condition is different, please adjust the specification
according to national standard.
⑧
The circuit breaker should include magnetic trip function and thermal trip function so that system
can be protected from short circuit and overload.
⑨
An all-pole disconnection switch having a contact separation of at least 3mm in all poles should
be connected in fixed wiring.
1.5.2 Circuit Diagram
Circuit diagram of GMV-224WM/E-X, GMV-280WM/E1-X and GMV-280WM/E-X